Laserfiche WebLink
May-05-2003 04:45pm From- • T-721 P.002/007 F-766 <br /> Triangle Environmental, Inc. <br /> 2525 West Burbank Blvd.,Burbank,CA 91505-2302 <br /> (818)840-7020 (818)840-6929 <br /> UST TESTING SYSTEMS SUMMARY <br /> Precision Underground Storage Tank System Leak Test <br /> Client: <br /> Conoco Phillips Co. <br /> 1500 North Priest Drive <br /> Tempe, AZ 85281 Test Date 6/6/2002 <br /> Kathy Strickland <br /> (602)728-7149 <br /> Facility: 2708671 Work#: 1290I008 <br /> 8606 THORNTON RD County: SAN JOAQUIN <br /> STOCKTON, CA 95209 Cross Street: DAVIS <br /> Tank Test System Tank Line <br /> # Product Capacity Type Rare/RemultR Ullage Result [tate/Result LID Rcsult <br /> I Unleaded Regular 9816 N/A N/A 0.000 PASS PASS <br /> 2 Unleaded Premium 9816 N/A NIA 0.000 PASS PASS <br /> 3 Unleaded Plus 9816 N/A N/A 0.000 PASS PASS <br /> Certified By; Technician: Tom Corcoran State Lic.#s: 02-1626 <br /> ® Mfgr's#1: TEI-067 <br /> VR-7539 <br /> Comments- <br /> Compliance P-L/TST,monitor certification,Grounding. Stage II Pressure Decay,Vapor Blockage&A/L <br /> This precision tank testing system has been third party evaluated according to the guidelines of the EPA <br /> procedures for annual leak detection systems and found to exceed the criteria of detecting a leak of 0.10 <br /> gph with a Pd>95%and Pfa<5%as required by Local,State and Federal PPA UST Technical <br /> Standards Part 280 for precision testing systems. <br />