May-05-2003 04:45pm From- • • T-721 P.003/007 F-786 <br /> Triangle Environmental, Inc. <br /> SYSTEMS TANK, LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Facility # 270$671 <br /> Tank #: 1 Test Date: 6/6/2002 <br /> Product: Unleaded Regular Work-9: 12901008 <br /> Test Method: Test Method: R.J.FTA <br /> Capacity_ 9816 Manufacturer: VaporIess <br /> Diameter(in): L/D Model: LD2000 <br /> Product Level(in): L/D Serial#: 01071422 <br /> Liquid Volume(Gals): rine Drain Back(ml): 58 <br /> Liquid Percent(%): L/D Trip Time(see): 2 <br /> Specific Gravity: Holding Pressure(psi): 26 <br /> Coef of Expansion: Metering Pressure(psi): 21 <br /> Water On Tank(in): LID Test Rate(gph)- 2.9 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): New Leak Detector? Yes <br /> Head Pressure(psi): <br /> Test Start Time <br /> Test End Time: Test Method: TEI LT-3 <br /> Test Rate(gph): Pump Brand: Red Jacket <br /> Test Result: N/A System Type: Pressure <br /> Line pressure(psi): 50 <br /> Line Start Time: 10:30 AM <br /> Test Method: ULLAGE Line End Time: 10.45 AM <br /> UllageVolume(gals.): Line Strut Level: 260 <br /> Ullage Test Time: Line End Level: 260 <br /> Ullage Vacuum,(psi): Line Test hate(gph): 0.000 <br /> Ullage Result: N/A - Line Test Result: PASS -- <br /> Replaced LD <br /> 2 <br />