Laserfiche WebLink
May-05-2003 04:46pm From- T-721 P.005/007 F-786 <br /> Triangle Environmental, Inc. <br /> SYSTEMS TANK, LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Facility # 2708671 <br /> Tank #: 3 Test Date: 6/6/2002 <br /> Product: Unleaded Plus Work N: 12901008 <br /> 70 Test Method: Test Method: R.J.FTA <br /> Capacity: 9816 Manufacturer: Vaporless <br /> Diameter(in): L/D Model: LD2000 <br /> Product Level(in)-- L/D Serial#: 53509 <br /> Liquid Volume(Gals): Line Drain Back(ml): 110 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity 7 Holding Pressure(psi): 28 <br /> Coef.of Expansion_ Metering Pressure(psi): I6 <br /> Water On Tank(in). L/D'fest Rate(gph): 2,9 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): New Leak Detector? No <br /> Head Pressure(psi): <br /> Test Start Time: <br /> Test End Time: Test Method: TEi LT-3 <br /> Test Rate(gph): Pump Brand: Red Jacket <br /> Test Result: N/A System Type: pressure <br /> Line Pressure(psi): 50 <br /> Line Start Time: 10:30 AM <br /> Test Method: ULLAGE Line End Time: I0,45 AM <br /> UlIageVolume(gals.): Line Start Level: 330 <br /> Ullage Test Time: Line End Level: 330 <br /> Ullage Vacuum(psi): Line Test Rate(gph): 0,000 <br /> Ullage Result: N/A — Line Test Result: PASS - <br /> 4., a <br /> 4 <br />