Laserfiche WebLink
May-05-2003 04:45pm From- • • T-721 P.004/007 F-786 <br /> Triangle Environmental, Inc. <br /> SYSTEMS TANK, LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Facility # 2708671 <br /> Tank #: 2 Test Date: 6/6/2002 <br /> Product: Unleaded Premium Work ft; 12901008 <br /> �11, <br /> Test Method: Test Method: R.J.FTA. <br /> Capacity: 9816 Manufacturer: Red Jacket <br /> Diameter(in): L/D Model: FX <br /> Product Level(in): L/D Serial#: 9492 i <br /> Liquid Volume(Gals): Line Drain Back(ml): 62 <br /> i <br /> Liquid Percent(%): L/D Trip Time(sec); 2 <br /> Specific Gravity: Holding Pressure(psi): 24 <br /> Coef. of Expansion: Metering Pressure(psi): 9 <br /> Water On Tank(in): LID Test Rate(gph): 2.9 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): New Leak Detector? No <br /> Head Pressure(psi): AFI a C tl^qi9 y <br /> Test Start Time: <br /> Test End Time: Test Method: TEl LT-3 <br /> Test Rate(gph): Pump Brand: Red Jacket <br /> Test Result: N/A System Type: Pressure <br /> Line Pressure(psi): s0 <br /> Line Start Time: 11:00 AM <br /> Test Method: IJLLA•GE Line End Time: 11:1 S AM <br /> Line Stari Level: 310 <br /> UllageVolume(gals.): <br /> Uilage Test Time: Line End Leve]: 310 <br /> Line Test Rate(gph): 0.000 <br /> Ullage Vacuum(psi): <br /> Line Test Result: PASS <br /> Ullage Result: N/AINNS <br /> _— <br /> M(�J�^"� <br /> 3 <br />