• <br /> Triangle Environmental, Inc. <br /> 2525 West Burbank Blvd.,Burbank,CA 91505-2302 <br /> (818)840-7020 (818)840-6929 <br /> UST TESTING SYSTEMS SUMMAR Y SHEET <br /> Precision Underground Storage Tank System Leak Test <br /> Client: <br /> Conoco Phillips Co. Facility # 2708671 <br /> 1500 North Priest Drive <br /> Tempe, AZ 85281 Test Date: 5/28/03 <br /> Kathy Strickland <br /> (602)728-7149 08671 <br /> Facility: 2708671 Work#: 20000838 <br /> Facility# 2708671 County: SAN JOAQUIN <br /> 8606 THORNTON RD Cross Street: DAVIS <br /> STOCKTON, CA 95209 <br /> Tank Test System Tank Line <br /> # Product Capacity Type Rate/Results Ullage Result Rate/Result UD Result <br /> 1 Unleaded Regular 9816 System 4000 N/A N/A 0.005 PASS PASS <br /> 2 Unleaded Premium 9816 System 4000 N/A N/A 0.000 PASS PASS <br /> 3 Unleaded Plus 9816 System 4000 NIA N/A — -0.005 PASS PASS <br /> Certified By: Technician: Tom Corcoran State Lic.#s: 02-1626 <br /> Mfgr's#: TEI-067 <br /> VR-7539 <br /> Comments: <br /> Stage II A/L,pressure decay&vapor blockage pretest. Compliance P-L/TST, monitor certification K IF. <br /> This precision tank testing system has been third party evaluated according to the guidelines of the EPA <br /> procedures for annual leak detection systems and found to exceed the criteria of detecting a leak of 0.10 <br /> gph with a Pd >95%, and Pfa<5% as required by Local,State and Federal EPA UST Technical <br /> Standards Part 280 for precision testing systems. This SB-989 secondary containment testing SN stem <br /> exceeds the criteria for detection as required by state and local agencies. <br /> UPS result to Roseville <br />