Triangle Environmental, Inc. <br /> SYSTEMS TANK, LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Facility # 2708671 <br /> Tank #: 1 Test Date: 5/28/03 <br /> Product: Unleaded Regular Work#: 20000838 <br /> 6100 Imam <br /> AKS .ESTRESUL <br /> Test Method: System 4000 Test Method: R.J.FTA <br /> Capacity: 9816 Manufacturer: Vaporless <br /> Diameter(in): L/D Model: LD2000 <br /> Product Level(in): L/D Serial#: 01051422 <br /> Liquid Volume(Gals): Line Drain Back(ml): 42 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: Holding Pressure(psi): 24 <br /> Coef. of Expansion: Metering Pressure(psi): 21 <br /> Water On Tank(in): L/D Test Rate(gph): 3.0 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): New leak detector? No <br /> Head Pressure(psi): <br /> SiJL <br /> Test Start Time: <br /> Test End Time: Test Method: TEI LT-3 <br /> Test Rate(gph): Pump Brand: <br /> Test Result: N/A System Type: Pressure <br /> -- — Line Pressure(psi): 52 <br /> TTLLAGETEST REST Line Start Time: 11:15:00 AM <br /> Test Method: ULLAGE Line End Time: 11:30:00 AM <br /> UllageVolume(gals.): Line Start Level: 320 <br /> Ullage Test Time: Line End Level: 325 <br /> Ullage Vacuum(psi): Line Test Rate(gph): 0.005 <br /> Ullage Result: N/A Line Test Result: PASS <br /> " <br />