Laserfiche WebLink
Triangle Environmental, Inc. <br /> SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Facility # 2708671 <br /> Tank #: 3 Test Date: 5/28/03 <br /> Product: Unleaded Plus Work#: 20000838 <br /> x4 Shp <br /> ,.. ETE .. ES RF�iJ,I. <br /> nm <br /> Test Method: System 4000 Test Method: R.J.FTA <br /> Capacity: 9816 Manufacturer: Red Jacket <br /> Diameter(in): L/D Model: FX-2 <br /> Product Level(in): L/D Serial#: 9492 <br /> Liquid Volume(Gals): Line Drain Back(ml): 110 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: Holding Pressure(psi): 24 <br /> Coef.of Expansion: Metering Pressure(psi): 12 <br /> Water On Tank(in): L/D Test Rate(gph): 2.9 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): New leak detector? No <br /> Head Pressure(psi): <br /> �Il <br /> Test Start Time: _ u, <br /> Test End Time: Test Method: TEI LT=3 <br /> Test Rate(gph): Pump Brand: <br /> Test Result: N/A System Type: Pressure <br /> Line Pressure (psi): 52 <br /> L,AGE Line Start Time: 11:15:00 AM <br /> �.,.. ... . r,. .-. ax = _.a. <br /> Test Method: ULLAGE Line End Time: 11:30:00 AM <br /> UllageVolume(gals.): Line Start Level: 330 <br /> Ullage Test Time: Line End Level: 335 <br /> Ullage Vacuum(psi): Line Test Rate(gph): 0.005 <br /> II <br /> Ullage Result: N/A Line Test Result: PASS <br /> COM11IE1V TS ' -- — — <br /> 3 <br />