or Tanknology <br /> SECONDARY CONTAINMENT TEST RESULTS <br /> SITE NAME: CHEVRON #98264 98264 DATE: 05/24/2002 WORK ORDER 2222260 <br /> SITE ADDRESS: 3775 TRACY BLVD @ 1-205 TRACY CA 95376 <br /> REASON FOR TEST: lGroundwater Level(" from grade): <br /> TANK INFORMATION AND INTERSTITIAL TESTS <br /> Dia. Depth Start Initial Finish Final Pass/ <br /> Tank Product Tank Size Material Manufacturer ('( Test Method Time Level Time Result Fail <br /> 1 SUPREME 11849 118 DW FIBERG Xerxes 72 Vacuum 09:28 10 .•H9 10'.32 10 ,H9 PASS <br /> 2 PLUS 11849 118 DW FIBERG Xerxes 74 Vacuum 09:28 10 "Hg 1032 10 •SHB PASS <br /> 3 UNLEADED 11849 118 DW FIBERG Xerxes 74 Vacuum 09'.28 1D ••H9 10:32 10 •H9 PASS <br /> 4 <br /> 5 <br /> 6 <br /> 7 <br /> 8 <br /> Comments <br /> LINE INFORMATION AND INTERSTITIAL TESTS <br /> Dia. Len. Volume Start Initial Finish Final Pass/ <br /> Tank Product Material Manufacturer Test Method <br /> feet (gallons) Time Level Time Result Fail <br /> 1 SUPREME 2.00 231 DW FIBERG Smith Pressure 08:20 2.5 psi 09.35 25 psi PASS 1, <br /> 2 PLUS 2.00 236 DW FIBERG Smith Pressure 08:29 2.5 psi 0935 2.5 psi PASS <br /> 3 UNLEADED 2.00 231 DW FIBERG Smith Pressure 0805 2.5 psi 0919 2.5 psi PASS <br /> 4 <br /> 5 <br /> 6 <br /> 7 <br /> 8 <br /> Comments'. <br />