Laserfiche WebLink
. ' Tanknokogy Test Date. 05/24/2002 <br /> SECONDARY CONTAINMENT TEST RESULTS Work Order. 2222260 <br /> SUMP TESTS <br /> Tank or Disp Model or Diam./WidtWLength Depth Start Initial Level Finish Final Pass/ <br /> Type 8 Manufacturer Material (•) (•) Test Method Time Level a Time Result Fail <br /> STP Sump SUP Phil-Tice Fiberglass 48 72 Hydrostatic-VPLT 09:04 75 gals • -.04239 09:34 +.662 gPh Fail <br /> STP Sump PLS Phil-Tice Fiberglass 48 74 Hydrostatic-VPLT 09:05 75 gals -.00080 09:35 +.012 gph Pass <br /> STP Sump REG Phil-Tile Fiberglass 48 74 Hydrostatic-VPLT 10:33 75 gals -.00045 11:03 +.007 gph Pass <br /> Dispenser Pan 1/2 Phil-Tile Fiberglass 27/51 26 Hydrostatic-VPLT 10:38 2' -.00020 10:51 +.005 gph Pass <br /> Dispenser Pan 314 Phil-Tice Fiberglass 27/51 26 Hydrostatic-VPLT 10:32 2- -.00050 1046 +.012 gph Pass <br /> Dispenser Pan 5/6 Phil-Tice Fiberglass 27/51 26 Hydrostatic-VPLT 08:32 2• +.00013 08:47 -.003 gph Pass <br /> Dispenser Pan 7/8 Phil-Tite Fiberglass 27/51 26 Hydrostatic-VPLT 08:39 2' -.00007 08:54 +.002 gph Pass <br /> Dispenser Pan 9/10 Phil-Tice Fiberglass 27/51 26 Hydrostatic-VPLT 12:27 2' -.00135 12:42 +.032 gph Pass <br /> Dispenser Pan 11/12 Phil-Tite Fiberglass 27/51 26 Hydrostatic-VPLT 12:21 2" -.00053 12:36 +.013 gph Pass <br /> Comments: Sup failed above collar/riser connection. Will pass below connection. <br />