Laserfiche WebLink
SWRC$,January 2002 Page 7 of 7 <br /> 4.TANK ANNULAR TESTING <br /> Test Method Developed 13y: ©Tank Manufacturer ®Industry Standard 0 Professional Engineer <br /> 0 Other(Spec) <br /> Test Method Uses: O Pressure ®Vacuum ©hydrostatic <br /> 0 Other(Specify) <br /> Test ui ent Used:0 TO 30"HG.GLYCERIN FILLED VACCUM GUAGES Equipment Resolution:0.1"HG. <br /> Tank#1 Tank# Tank# Tank# <br /> Is tank Exempt From Testing?' NO <br /> Tank Cupac44,000 GAL. <br /> Tank Material: FIBERGLASS <br /> Tank Manufacturer. OWENS CORNING <br /> Product Stored: DIESEL <br /> Wait time between applying <br /> pressurelvacuumfwater and starting F 30 MIN. <br /> test: <br /> Test Start Time: 11.00 AM <br /> Initial Reading(Rt): 10" HG. <br /> Test End Time: 12:00 PM <br /> Final Reading(R F): 10"HG. <br /> Test Duration: 1 HOUR <br /> Change in Reading(RF-Rt): 0 <br /> PasslF'ail'rhreshold or Criteria: 0 <br /> Teat Result: PASS <br /> Was sensor removed for testing? NA <br /> Was sensor property replaced and NA <br /> verified functional after testing? <br /> Comments-(include information on repairs made prior to lesiing, and recommended follow•-up for failed tesis) <br /> 'Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. (California Code of Regulations,Title 23,Section 2637(a)(6)) <br /> Revision: <br />