Laserfiche WebLink
FOR AUTHORIZED USER ONLY DO NOT TAMPER ITH THE SYSTEM <br /> r Alternative System Setup Procedures (with Power On) <br /> The 522 Remote Monitoring System can assign the dispensers with all dispensers powered on. <br /> This should only be done if it is difficult to follow normal procedures and if the controller <br /> serial numbers have been matched to the particular dispenser numbers. <br /> • 1. Plug the 522 Remote Monitoring System transformer into the dedicated outlet described in the <br /> previous section and as shown on pages 3-7. Turn on power to all dispensers. <br /> ■ 1. Press Escape to get to Main Menu <br /> Main Menu <br /> i Monitoring Mode <br /> 2. Press -a key until the following screen appears: <br /> i Main Menu <br /> System Setup <br /> 3. Press Enter <br /> Select Action <br /> i Assign Disp <br /> t 4. Press Enter <br /> Select Disp # <br /> Disp #01 <br /> 5. Press Enter <br /> Select Serial # <br /> 00000000 <br /> A serial number will be displayed—if the screen shows the correct serial number that matches <br /> the serial number written on the controller label that is installed in Dispenser 1, then press Enter. <br /> Otherwise, press up or down arrow key until the correct serial number is shown before pressing <br /> Enter. Follow this procedure for all other dispensers. <br /> P-4 <br />