Laserfiche WebLink
VM1 <br /> Vaporless Manufacturing, Inc. <br /> Quality Petroleum Equipment <br /> Solutions for Over 20 Years <br /> LDT-890 Test Form&VMI Warranty Checklist <br /> q <br /> October I ,2008 <br /> Test Information <br /> Date: 11/21/08 Test Company: EPIC Compliance 5vstems Inc <br /> Telephone: 209-814-6274 Contact : --Site I.D: Ouicki Kleen Address: 707 F Yo mite Ave <br /> City: Man a State: CA Zip: 95336 <br /> Type of Test Equipment: LDT 890 <br /> Submersible Pump Identification <br /> MFG: RFD JACKET Model No: Serial No: <br /> Leak Detector Identification <br /> MFG: FE PETRO Model No: STP-MLD Serial No: 0710-1150 <br /> Replacement Leak Detector Identification <br /> MFG: Model No: Serial No: <br /> Line Conditions <br /> 1.Type of Pipe: FG 2.Diameter of Pipe: 2" 3.Length of Pipe: 100' <br /> 4.Burial Depth of Leak Detector: 24" S.Kind of Fuel: 87 6.Date of Last Line Test: - <br /> Test Conditions <br /> 1.Operating Pump Pressure:23 2.Gallon per hour test rate: 3 @ 10 psi <br /> 3.Static Line Pressure(Pump Off): 18 4.Bleedback Test(Pump Off): 140 ml. <br /> 5.Step-through time to full Flow 2 seconds(0 psi.to full pump pressure,no leak) <br /> S.Leak detector stays in Leak Search Position with a 3 GPH leak-Yes: X PASS No: FAIL <br /> 7.Was the leak detector adjusted–Yes:_ No: X <br /> Symptoms <br /> 1.Won't find 3 GPH leak: 2.Stays in Slow Flow: <br /> 3.Other: <br /> —...*'**** If This Unit Is Returned Under Warranty Please Complete The Following <br /> Vaporless RGA#: Return By(Company): <br /> Telephone: Contact: <br /> Customer Control#: Address: <br /> City: State: Zip: _ <br /> (See Website-www.vaporless.com -Technical Bulletin 032805) <br />