VMI <br /> Vaporless Manufacturing, Inc. <br /> Quality Petroleum Equipment <br /> Solutions for Over 20 Years <br /> LDT-890 Test Form&VMI Warranty Checklist <br /> October 3006 <br /> Test Information <br /> Date: 11/21/08 Test Company: rPICCOMplianCeSYsteMS. Inc <br /> Telephone: 209-814-6274 _ Contact : <br /> Site I.D: O i ki Kleen _. Address: 707 F v„=ornite Ave <br /> City: Manteca _ State: CA Zip: 95336 <br /> Type of Test Equipment: LDT 890 <br /> Submersible Pump Identification <br /> MFG: RFD JACKET Model No: Serial No: <br /> Leak Detector Identification <br /> MFG: FE PETRO Model No: STP-MLD-D Serial No: 0709-1297 <br /> Replacement Leak Detector Identification <br /> MFG: Model No: Serial No: <br /> Line Conditions <br /> 1.Type of Pipe: FG 2.Diameter of Pipe: 2" 3. Length of Pipe: _50' _ <br /> 4. Burial Depth of Leak Detector: 24" 5.Kind of Fuel: Diesel 6.Date of Last Line Test:—__. <br /> Test Conditions <br /> 1.Operating Pump Pressure: 30_ 2.Gallon per hour test rate:2_ @ 10 psi <br /> 3.Static Line Pressure(Pump Off): 30 4. Bleedback Test(Pump Off): 150 ml. <br /> 5.Step-through time to full flow —seconds(0 psi.to full pump pressure,no leak) <br /> 6.Leak detector stays in Leak Search Position with a 3 GPH leak-Yes: X PASS No: FAIL <br /> 7.Was the leak detector adjusted—Yes: NO: X _ <br /> Symptoms <br /> 1.Won't find 3 GPH leak: 2. Stays in Slow Flow: <br /> 3. Other: <br /> If This Unit Is Returned Under Warranty Please Complete The Following <br /> Vaporless RGA#: Return By(Company): <br /> Telephone: _. _. Contact: <br /> Customer Control#: Address: <br /> City: State: _ Zip: <br /> (See Website-www.vaporless.com -Technical Bulletin 032805) <br />