ARB Approved IOM - Healy Phas*..,:VR System-VR-201-A (CAS-9961) y Page 16 <br /> INSTALLATION INSTRUCTIONS for <br /> HEALY SYSTEMS, INC. <br /> CLEAN AIR SEPARATOR <br /> The Model 9942, Healy Systems Clean Air Separator Installation consists of a 400 gallon steel tank <br /> assembly (9961) that contains a fuel resistant bladder to contain excess gasoline vapors that may <br /> develop in gasoline storage tanks during idle periods of gasoline dispensing facility operation. The <br /> tank assembly weighs approximately 800 pounds which makes it necessary to have a power <br /> assisted lifting device available at the installation site to remove the tank from the transportation <br /> vehicle and place it on the required concrete pad (see drawing B9900-9945). The pad (level within <br /> 1/8"!foot) is located within 100 feet to the storage tank vent lines. The pad is a requirement of this <br /> installation. DO NOT PLACE THE TANK DIRECTLY ON THE GROUND OR ASPHALT SURFACE. <br /> NOTICE: The installer is responsible to ensure that the installation meets the latest edition <br /> requirements of NFPA 30A, Chapter 10. No electrical connections are required. The tank <br /> securement method shown in drawing B9900-9945 shall be approved by the local authority having <br /> jurisdiction with respect to wind and seismic loading. <br /> In addition to the tank, there is a hardware kit that contains the following: <br /> 1 Pressure/Vacuum vent valve (See Exhibit 1 of VR-201-A for model number) <br /> 4 Locking 1" NPT Ball Valves <br /> 4 Pad locks (keyed alike) <br /> 1 Breather Assembly, Healy Model 9948 <br /> 1 Vapor Inlet Assembly, Healy Model 9956 <br /> 1 Float Check Valve Assembly, Model 9466G <br /> Reference the appropriate Healy Systems installation drawing (C9900-9942, C9900-9971, C9900- <br /> 9972 or C9900-9973 of this manual) for placement of the above parts for the vent stack <br /> configuration required by the local Authority Having Jurisdiction (AHJ) for the UST system. The <br /> local contractor is responsible to provide all necessary, galvanized piping, non-hardening, UL <br /> classified pipe joint compound and plumbing fittings. Additional Pressure/Vacuum (PN) vent valves <br /> to complete installation are not included in the hardware kit. Healy is not responsible for the <br /> warranty of any other PN vent valve purchased to complete installation. <br /> The tank arrives at the site assembled and tested. All plumbing should be done using 1" galvanized <br /> steel pipe (Schedule 40) and approved nipples, as called out in the installation drawing appropriate <br /> for the site installation. Mounting hardware should be galvanized or stainless steel. Careful <br /> attention must be paid to the installation drawing appropriate for the site installation to assure proper <br /> operation of the bladder system. Do not inflate the bladder assembly after installation. <br /> it is important that the tank be secured to the concrete pad as shown in drawing B9900-9945 of this <br /> manual to prevent any unintentional repositioning of the tank as the connecting plumbing to the vent <br /> system is accomplished. <br /> Healy Systems, Inc. Website: http://www.healysystems.com <br /> 18 Hampshire Drive Email: sales@healysystems.com <br /> Hudson, New Hampshire 03051 USA Telephone: 603.882.2472 <br /> ARB Approved Installation, Operation and Maintenance Manual (April 8, 2005) Fax::603.882.5189 <br /> Healy Systems, Inc. —the innovative leader or Stage 11 vapor recovery equipment <br />