Laserfiche WebLink
CERTIFICATE OF UNDERGROUND STORAGE TAN TEM TESTING <br /> �,, � <br /> P,TAi. H((F� ALTH <br /> NDE ENVIRONMENTAL CORPORATION rZ;i't!J klr�vIU4 <br /> 20000 Mariner Avenue, Suite 500 <br /> Torrance, California 90503 128 - PM 2; 00 <br /> (310) 542-4342 <br /> Test Date: 7 Jun 1993 Work Order#: 961005 <br /> Client: THE SOUTHLAND CORPORATION Site : 7-11 #2235-21756 <br /> 295 W. CROMWELL, #104 853 E. YOSEMITE AVE. <br /> FRESNO , CA 93711 MANTECA CA 95336 <br /> Attn: JEFF SIMONSON <br /> The following tests were conducted at the site described above in accordance with all applicable portions of Federal,NFPA,and Local regulations. <br /> TANK SYSTEM INFORMATION <br /> Tank Tank Product Vapor Recovery <br /> Tank Capacity Diameter Level Tank <br /> No. Gallons Inches Product Inches Material Stage I Stage IT <br /> 1 9, 980 95 PREMIUM 50.50 STEEL COAX BALANCE <br /> 2 9, 980 95 MIDGRADE 41.00 STEEL COAX BALANCE <br /> 3 9, 980 95 UNLEADED 48.75 STEEL COAX BALANCE <br /> TESTING RESULTS <br /> VPLT Wetted Vent & Leak Leak <br /> Volume Portion Ullage Vapor Product Detector Detector <br /> Tank Change of Tank Test Lines Lines Present? Results <br /> No. (gph) Pass/fail Pass/Fail Pass/Fail Pass/Fail Yes/no Pass/Fail <br /> 1 -0.001 PASS PASS PASS PASS YES PASS <br /> 2 -0 . 002 PASS PASS PASS PASS YES PASS <br /> 3 -0 . 027 PASS PASS PASS PASS YES PASS <br /> NDE appreciates the opportunity to serve you,and looks forward to working with you in the future.Please call any time,day or night,when you need us. <br /> NDE Customer Service Representative Testing conducted by <br /> F. MILLER M. LEVESQUE <br /> !y <br /> Reviewed by: Technician certification no.: <br /> B 'aminAlicea 1405 <br />