Laserfiche WebLink
Test Date: 7 Jun 1993 Work Order#: 961005 <br /> TANK TESTING DATA <br /> Tank 1 Tank 2 Tank 3 Tank 4 Tank 5 Tank 6 <br /> Product: PREMIUM MIDGRADE UNLEADED <br /> True Capacity-gal : 9, 980 9, 980 9 , 980 <br /> Manifolded tanks : NO NO NO <br /> Manifolded Vents : YES YES YES <br /> Tank Bottom <br /> to top of fill-in: 124 124 125 <br /> Fill pipe length-in: 29 29 30 <br /> Tank diameter-in: 95 95 95 <br /> Tank Bottom <br /> to top of grade-in: 132 133 135 <br /> Fill pipe diameter-in 4 4 4 <br /> Fluid Level-in: 50 . 50 41 . 00 48 .75 <br /> Fluid Volume-gal: 5 , 391 4 , 123 5 , 157 <br /> Water in tank-in: 0 0 0 <br /> Specific Gravity: 0 .748 0 .746 0 .743 <br /> Tank Construction: STEEL STEEL STEEL <br /> OFT/UFT: UFT UFT UFT <br /> No. thermistor: 5 5 5 <br /> Ground Water level-in 0 0 0 <br /> How determined: WELL WELL WELL <br /> Test start time: 19 : 56 20 : 01 20 : 07 <br /> Test finish time: 21: 57 22 : 03 22 : 09 <br /> Total temperature <br /> change (degrees F) : -0 .014 -0 . 011 -0 . 058 <br /> Total fluid level <br /> change (inches) : 0 . 000 0 . 000 -0 . 001 <br /> Leak Rate (GPH) : -0 .001 -0 . 002 -0 . 027 <br /> Pass/Fail : PASS PASS PASS <br /> NDE EnvirontrcaW Corporation-20000 Mariner Avenue Ste 500-Totrma,CA.90503-(310)542-4342 <br /> Page 1 <br />