7. UNDER-DISPENSER CONTAINMENT(UDC)TANG <br /> Test Method Developed By: ❑ UDC Manufacturer - E Industry Standard ❑ Professional Engineer <br /> ❑ Other(Specify) <br /> Test Method Used: ❑ Pressure ❑ Vacuum E Hydrostatic <br /> ❑ Other(Specify) <br /> Test Equipment Used: Incon TS-STS Sump Test System Fquipment Resolution: +1-0.002" <br /> [IDC# T12 UDC# UDC# L1DC# <br /> UDC Manufacturer: Environ <br /> UDC Material: Plastic <br /> UDC Depth: 30" <br /> Height from UDC Bottom to Top 1211 <br /> of Highest Piping Penetration: <br /> Height from UDC Bottom to 8i1 <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to <br /> testing: Goad <br /> Portion of UDC Tested 4"Above Pen. _ <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both ❑Yes❑ No E NA ❑Yes❑No ®NA ❑Yes❑ No N NA ❑Yes❑No E NA <br /> product and water)?` <br /> Turbine shutdown response time N/A _ <br /> Is system programmed for fail- ❑Yes❑No ®NA ❑Yes❑No U NA ❑ Yes ❑ No ENA ❑Yes❑No E NA <br /> safe shutdown?" <br /> Was fall-safe verified to be ❑Yes❑No ENA ❑ Yes❑No ENA ❑Yes❑No ENA ❑ Yes❑No ENA <br /> operational?* <br /> Wait time between applying <br /> pressure/vacuum/water and 30 minutes <br /> starting test <br /> Test Start Time: 12;45 PM <br /> Initial Reading(RI): 1.4695 <br /> Test End Time: 01:00 PM <br /> Final Reading(RF); 1.4693 <br /> Test Duration: 15 min. <br /> Change in Reading(Rr-R,): -0.0002 <br /> Pass/Fail Threshold or Criteria: +/-0.002 <br /> Test Result: Pass <br /> Was sensor removed for testing? Yes <br /> Was sensor properly replaced and <br /> verified functional after testing? Yes <br /> Comments--(include information on repairs»rade prior to testing, and reconrnzended folloiv-up for failed tests) <br /> Sensor functionality was not confirmed.This procedure is not part of the Secondary Containment Testing scope of work. <br /> If the entire depth of the UDC is not tested, specify how much was tested, If the answer to any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (Sce SWRCB LG-l60) <br />