7. UNDER-DISPENSER CONTAINMENT(UDC) TESTJNG <br /> Test Method Deveiaped By: ❑ ODC Manufacturer ® Industry Standard U Professional Engineer <br /> ❑ Other(specify) <br /> Test Method Used: ❑Pressure ❑ Vacuum ® Hydrostatic <br /> ❑ Otlfer.(SpecifyJ <br /> Test Equipment Used: Incon TS-STS Sump Test System Equipment Resolutio[t: +/-0..1102" <br /> UDC# 9 t4_ A VOC# 11112 UDC# VDC# <br /> UDC Manufacturer: Environ Environ <br /> UDC Material: Plastic Plastic <br /> UDC Depth: 28" 28" <br /> Height from UDC Bottom to Top 11" ll" <br /> of Highest Piping Pwlctrat on: <br /> f4eighi from UDC Bottom to 5" 511 <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to <br /> testing: Good Good <br /> Portion of UDC Tested 4" Above Pen 4"Above Pen. <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both ❑Yes❑No n NA ❑Yes❑No U NA ❑Yes❑ No ®NA ❑ Yes❑ No RNA <br /> product and)eater)?* <br /> Turbine shutdown response time, NIA NIA <br /> Is system prograrruned for fail- ❑Yes❑No ®NA ❑'Yes❑No ®NA ❑Yes❑No ®NA ❑Yes❑ No R.NA <br /> safe shutdown?' <br /> Was fail-safe verified fo be ❑yes El No 19 NA ❑Yes❑No E NA ❑Yes❑No U NA ❑ Yes.❑ No U NA <br /> operational? - <br /> Wait <br /> erational?Wait bine between applying <br /> pressure/i aciiaiiVwater'and <br /> 30 minutes 34 minutes <br /> starting test <br /> Test Start Time: 12:16 PM <br /> Initial.Reading:(R;): 5.8986 <br /> Test End Time: 12:31 PM <br /> Ficial Reading(RF): 5.8978 <br /> Test Duration: 15 min. 15 min. <br /> Change in IZeadin'g(RT;-I;4)-: -0.0008 <br /> Pass/Fail.Threshold or Criteria: +/-0.002 +1-0,002 <br /> Test.Result; vulalial Fail Pass <br /> Was sensor removed for testing? Yes y <br /> Was sensor properly replaced Bind <br /> verified functional after testing? Yes Yes <br /> Cam m elri is— (Include il!fOr malion:on repoirs made prior to testing, and reeoumrended,folloir-rip.for fulled tests) <br /> Sensor functionality was not confirmed. This procedure is not part of the Secondary Containment Testing scone of`vork. <br /> 9110 torn penetrations. <br /> OCT 2 6 2017 <br /> ENV1RONMENTAL HEALTH <br /> PERMITISFRMES <br /> If the entire depth of theUDC TDC is not tested,specify how much was tested. If the answer to Ayn of tate questions indicated vvith.an <br /> asterisk N is"NO"or"NA",the entire UDC must be tested, (See SWROB LG-160) <br />