Laserfiche WebLink
7. UNDER-DISPENSER CONTAINMENT(UDC) TESTING <br /> Test Metfiod Developed By: ❑ UDC Ivlalt.4tfacturer ® Industq Standard ❑ ProfessionatEngincer <br /> ❑ Other(Specifu) <br /> Test Method Used: ❑Pressure ❑ Vacuum 0 Hydrostatic. <br /> p Other(Specify) <br /> Test Equipiiient Used: Incon TS-STS sump Test system Equ pMent Resolution: +/-0.902" <br /> UDC.# 112 UDC# &4 UDC# UDC 0 <br /> UDC Manufacturer: Environ Environ Environ )environ <br /> UDC Material: plastic Plastic Plastic Plastic <br /> UDC De the 34" 34" 30+' 30" <br /> Height from UDC Bottom to Top 11" 11" 11'+ IV <br /> of Highest Piping Penetration; <br /> Height from UDC Bottom to 5+' 5" 5" 5" <br /> Lowest EIectrical Penetration: <br /> Condition of UDC prior to <br /> testing: Good Good Good Good <br /> Portion of UDC Tested 4" Above p n 4" n 4" Above Pen, " A n <br /> Does turbine shut down when <br /> UDC sensor detects.liquid(both ❑Yes ❑ No E NA ❑ Yes ❑ No ®NA ❑ Yes.El No .0 NA ❑Yes 0 No ®NA <br /> product and-vvater)7` <br /> Turbine shutdown response time N/A NIA N/A NIA <br /> Is system programmed for fail- ❑ Yes❑TNo 2 NA ❑ Yes❑ No ®NA ❑ Yes❑No U.NA ❑Yes❑ No ®NA. <br /> safe shutdown?' <br /> Was failsafe 9erified.to be El Yes❑No 0 NA E❑ Yes❑No ®NA ❑ Yes❑No Z NA ❑Yes El Na. ®.NA <br /> o eration4ff <br /> Wait time bet-ween applying <br /> pressure/vacuuin/rvater.aild 30 minutes 30 minutes 30 minutes 30 minutes <br /> starting test <br /> Test Start Time: 11:26 AM 11:26 AM <br /> initial Reading(Rj): 4.2429 5.358 <br /> Test End Time: 11:41 AM 11:41 AM <br /> Final Reading(RF): 4.204 5.3573 <br /> Test Duration: 15 min. 15 min. 15 min. 15 min. <br /> C11FR in Readit1g(RF-Rl): -0.0389 -0.0007 <br /> Pass/Fail Threshold or Criteria: +/-0.002 +/-0.002 +/-0.002 +/-0.002" <br /> Test Result: Fail Visual Fail Pa" Visual Foil <br /> Was sensor removed.for testing? Yes Yes Yes Yes <br /> Was sensor properly replaced,and <br /> verified functional after testin 7 Yes Yes Yes Yes <br /> COmnlents— (include h?formaliojr on repairs made prlof to lesting, cad recoy+ruefadedLolloii-r(p fat-failed tests) ^� <br /> Sensor functionality was not confirmed. This procedure is not part of the Secondary Containment Testing scope of work. <br /> -1/2 unable to locate leak. <br /> -3/4 and 7/8-torn penetrations. <br /> F. <br /> ENVIRONMENTAL HEALTH <br /> PERMITISERVICES <br /> If the entire depth of the UDC is not tested,specify how much was tested. If the answer to ate-of the questions indicated with an <br /> asterisk(*)is"NO"or"NX',the entire.UDC mus(be tested. (See 5WRCB LG-160)' <br />