Laserfiche WebLink
9. SPILLIOVERFILL CONTAINMENT BOXES <br /> Facility is Not Equipped With Spill/Overfill Containment Boxes LI <br /> Spill/Overfill Contaimnent Boxes are Present,but.wer@ Not Tested ❑ <br /> Test Method Developed By; C Spill Bupket.Manufaeturer ® Industry Standard ❑Professioiml Engineer <br /> ❑ O.ther(Specify) <br /> Test Method Used: p Pressure ❑ Vacuum ®hydrostatic <br /> El Other(Specify) <br /> Test Equipment Used: Incon TS-STS sump Test system Equipment Resolution: +1-0.002" <br /> ;r , Spill Box# T1-87-FB Shill BO\# T1-87-V13 Spill Box# '1'2-87413 Spill Box#T2-87-VB <br /> Bucket Diameter: 12" 12" 12" 12" <br /> Bucket Depth: <br /> Wait time behveen.applying <br /> pressure/vacuum/water and 30 minutes 30 minutes 30 minutes 30 minutes <br /> startin test: <br /> Test Start Time: 05:49 AM 06:12 AM 05:49 AM 06:12 AM <br /> Initial Reading(Rr): 3.2984 3.747 2.064 2.8989 <br /> Test End Ticne: 06:04 AM 06:27 AM 06:04 AM 06:27 AM <br /> Final Reading(RF); 3.2978 3.7406 0.3663 2.8951 <br /> Test Duration: 15 min. 15 min. 15 min. 15 min. <br /> Change in.Reading.(kr-R,): -0.0006 -0.0064 -1.6977 -0.0038 <br /> Pass/Fail Threshold or <br /> Criteria: +/-0,002" +/-0.002" +/-0.00211 +/-0.002 <br /> Test Result: Pass Fail rail Fail <br /> C0111I11 e1Mt5-{lnclude irrforrrratio)t.orr repaii.r rrtcrcle prior•to testing, alis]mcorrrmended follow-up fbr falledl tests) <br /> OCT 2 6 2017 <br /> ENVIKONmEN IAL REAL i�[— <br /> PERMITISERVI ES <br />