SPECIFIC NOTES: <br /> ES: <br /> AREA OUTLINED IS A CLASS 1, DIVISION 1(BELOW GRADE AND DISPENSER <br /> HOUSING) AND CLASS 1 DIVISION 2(ABOVE GRADE) HAZARDOUS AREA, <br /> AND SHALL CONFORM TO NEC ART, 500, 501 , 514, AND NFPA 30A. <br /> ALL CONDUITS ENTERING OR LEAVING THIS AREA SHALL HAVE SEAL--OFFS <br /> FITTINGS ON BOTH ENDS OF THE RUN, CONDUIT INSTALLED IN, ENTERING, <br /> PASSING THRU AND LEAVING THIS AREA INCLUDING ALL RISERS AND LAST- 2' OF <br /> ,[—EXISTING STORAGE U.G. RUN TO THE POINT OF CONNECTION TO THE ABOVE GROUND CONDUIT <br /> _ CONTAINER TO REMAIN --- SHALL BE THREADED RIGID METAL CONDUIT OR THREADED STEEL <br /> INTERMEDIATE METAL CONDUIT. RIGID NONMETALLIC CONDUIT COMPLY WITH <br /> ART, 347 SHALL BE PERMITTED WHERE BURIED UNDER NOT LESS THAN <br /> 2 FEET BELOW GRADE EXCEPT WHERE PROHIBITED 8Y LOCAL CODE OR <br /> 00 AUTHORITIES HAVING JURISDICTION. <br /> 3/4"C, 210+1#10 RECONNECT TO EXISTING CIRCUIT. <br /> °�-HXOXTWITH�GUAR CAL <br /> POSTS H R N PROVIDE PULL BOX WITH TRAFFIC COVER (PULL BOX SIZE AND LOCATION <br /> EXISTING FREEWAY SIGN w/ DEPEND ON FIELD CONDITION AND PER NEC ARTICLE 370-28 REQUIREMENTS) <br /> ° SHELL LOGO TO REMAIN TO INTERCEPT EXISTING CONDUITS AND CONDUCTORS TO EXISTING CANOPY, <br /> EXISTING " YONS'• 04 EXTEND SAME NUMBER AND SIZE OF CONDUITS AND CONDUCTORS TO NEW <br /> SIGN TO �IAI1 .�.,- =�' ---, LOCAT0N OF EXISTING RELOCATED CANOPY FOR CONNECTING EXISTING <br /> ' dXISTING ELt�IC DISPENSER POWER, DATA, INTERCOM, CANOPY LIGHTS, SPANDRELS, LIGHT WELL <br /> EXISTING VENT RISERS BOX TO REMAIN LIGHTS ETC.; TO ITS ORIGINAL CIRCUITS TO RESTORE TO ITS ORIGINAL <br /> I0 REMAIN FUNCTION. FIELD VERIFY ALL REQUIREMENT'S. <br /> ISERVICE 1 4 SEE SHEET E-3 FOR CONTINUATION, <br /> EXISTigG AIR/WATER EX SER E <br /> UNIT & REA LIGHT 1 MAIN TO REMAIN n <br /> i N COIRETE PAD 1 ° INTERFACE AND CONNECTION METHOD OF EXISTING CONDUIT, CONDUCTORS AND <br /> O <br /> - ��-- --_. O Rk� R <br /> _.... BRANCH CIRCUITING AT EXISTING CANOPY LOCATION AND RELOCATED CANOPY NEW <br /> _. w <br /> _.____ � .,,.;, .,;....:• LOCATION ARE SUBJECT TO ACTUAL SITE CONDITION WHICH WILL BE REVEALED AFTER <br /> tf ° ► RELOCATING EXISTING CANOPY AT THE FIELD. REFER TO SUGGESTED DETAIL THIS <br /> - SHEET AND USE THE MOST APPROPRIATE METHOD TO SUIT THE SITE CONDITION. <br /> , " SHOP DRAWING OF SUGGESTED APPROACH TO BE APPROVED BY CONSTRUCTION <br /> EX, PNL, A TO R MIN <br /> B TO REMAIN 1 1 ENGINEER PRIOR TO INSTALLATION. <br /> _....-. <br /> 6. REUSE EXISTING CONDUITS WHERE APPLICABLE, IN GOOD CONDITION, <br /> PERMITTED BY CODE AND CITY INSPECTOR. <br /> w EXISTINGLUBE BAY <br /> -- ,: �► 7 J-BOX ON NEW COLUMN WITH REQUIRED CONDUITS AND CONDUCTORS TO <br /> BUILDING TO REMAIN EXISTING PANEL (A-18,20,22,24,19,21 ,23,25,27,29,31) <br /> EXISTING "LYONS" EXISTING PARKING SPACE <br /> TO REMAIN TYRL AL �+ _ <br /> RESTAURANT �' ( :) r .._. _ <br /> �� �� � •� EXISTING WAST OIL._�E:ANK & <br /> TO REMAIN _..__. _`Z „CC_ CONCRETE SLA Ta REMAIN 1 <br /> I . su O 1 .% <br /> SEE SHEAT E-3 FOR DETAIL <br /> - 3 ::::::::.::............::::::..............: WALL TANKS TO REMAI3� <br /> INFORMAfTION <br /> 7 1 2 <br /> momm "I\, I <br /> FASVApn <br /> Y <br /> __ ­ .. C- ❑ ❑ ;';:;:.:.. .......:::::'"',; EXISTING PUBLIC TE PHONE <br /> r ELOCATE[� CANOPY Y EQUILON'S TO REMAIN (TYPICA F ) <br /> (( :,. <br /> r ENERAL GONTRACTOR5 .' . <br /> 11 }} 1.111, VOTE.—T �., <br /> QaK31} CIv#OVAPORC CO ERY <br /> 1 NEVA:':: N <br /> __ <br /> -----EXISTING AREA LIGHT <br /> : ' ❑ ❑ ❑ r N�"" ,�� <br /> CONCRETE BASE ��UH Til <br /> (PIRA SEFrv�)_LA_] LOCATED EA <br /> ❑ ,LI HT w N <br /> EXISTINGLSIGN - -. __.._ ..__.-�-_-- _ _ / iNG <br /> TO REMAIN <br /> NOTE! ALL EXISTING ITEMS ARE TO REMAIN <br /> UNLESS NOTED OTHERWISE. <br /> — RELOCATED "DRESSER WAYNE" MULTI- <br /> PRODUCT GASOLINE DISPENSER <br /> w/ CARD LEADERS, BLENDERS, <br /> � <br /> SINGLE HOSE EACH SIDE, & VAPOR <br /> BIB IB J AVAC NOZZLES (BY EQUILON'S <br /> GENERAL CONTRACTOR) <br /> (TYPICAL OF 4 DISPENSERS) <br /> LEGEND <br /> — - - -- -- UNDERGROUND CONDUIT RUN <br /> REMOVABLE <br /> TRAFFIC COVER <br /> �--- 8 ELECTRICAL SITE NOTES NUMBER <br /> + JUNCTION BOX TYPE AS NOTED <br /> -�---PULL BOX EXISTING PANEL/WIREWAY IE <br /> SIZE AS REQUIRED PANEL TO REMAIN <br /> CLASS 1 , DIVISION 1 AREA <br /> (BELOW GRADE & DISP. HOUSINGS) <br /> LASS 1 , DIVISION 2 AREA <br /> EXISTING CONDUITS & —EXISTING BUILDING 0 10 20 30 (ABOVE GRADE) <br /> FROM' VIEW OF PULL BOX SEAL TO REMAIN WALL TO REMAIN <br /> GRAPHIC SCALE X X INDICATES CONDUIT SEAL <br /> REMOVABLE I <br /> TRAFFIC COVER <br /> CONTRACTOR TO CONTACT <br /> EXISTING FINISHED GRADE <br /> FINISHED GRADE ELECT WIRE WAY UNDERGROUND SERVICE ALEFT <br /> I1 <br /> 1 -800-642-2444 <br /> 642-2444 <br /> PULL BOX, SEE FRONT VIEW j, __l GALL SSA/SC <br /> (FULL BOX SIZE & LOCATION FOR UNDERGROUND LOCATING <br /> SPEND ON FIELD CONDITION _ _ 2 WORKING DAYS BEFORE YOU DIG <br /> & PER NEC ARTICLE 370--28 <br /> REQUIREMENTS ---- <br /> EkST. SITE CONDUITS <br /> TO BE INTERCEPTED <br /> AAPROVEIJ <br /> PROVIDE NEW SEAL--OFF 0RAw1NC �ssv�D �aR DAr Ass sN�u REVISIONS SHELL OIL COMPANY <br /> FITTINGS FOR CONDUITS � ---__ ___ <br /> EXTEND NEW CONDUITS AND FROM HAZARDOUS AREA sH��c �NcrN��'R No. DATE BY �COMMENTs <br /> HOUSTON, 'TEXAS <br /> CONDUCTORS TO NEW LOCATION --OF RELOCATED CANOPY ENGNNEER”SA ----FABRIC -- -- ,--- ---- <br /> BACKFILL MATERIAL; - <br /> PEA RAVEL. BELOW � INC .� � NAM�',_�_______ti _� __ __.��-____ _ _ <br /> CONCRETE OR ASPHALT MECHANICAL, ELECTRICAL PLUMBING ENERGY ELECTRICAL SITE PLAN <br /> PCANNlNG <br /> GRADE COVERSIDE VIEW 15550-B ROCKFIELD BLVD., #220 TEL: (949) 837-3133 ___ <br /> IRVINE, CA, 92518 FAX. (949) 837-9568 PF '"`r PLANS PREPARED BY. 3011 W. BENJAMIN HOLT DR. & FREEWAY OFF-RAMP <br /> NOTA: ero coNTRAcr DocuME'NT ' STOCKTON CALIFORNIA <br /> ONLY EXPLOSION PROOF UNIONS, COUPLINGS, ELBOWS AND CONDUIT BODIES SHALL BE These drawings, specifications, calculotions, designs & arrangements are and NOT F-OR CONSTRUCTION -�^ '' E'NGINE`ERING ' <br /> USED WITHfN PULL BOX. ALL BOXES, FITTINGS AND JOINTS SHALL BE THREADED FOR shall remain the sole property of PROCEDURE ENGINEERS INC,. All rights are CONSTRUCTfON � � PLANNING ENGINEERING CONSTRUCTION MANAGEMENT SCALE: AS NOTED <br /> CONNECTION TO CONDUIT AND SHALL BE EXPL65I0N PROOF TYPE, <br /> reserved for specific p(oject that these pians are prepared for, Dupiications 00 Nor USE FOR CONST, 1243 ALPINE ROAD, SUITE 109 DATE: 10/29 99 WIC 204-7524-4404 <br /> PULL BOX WITH CONDUIT` S'"�""UB—UP DETAIL of any kind for any purpose without any expressed written permission of uNI�ESS BATHSIG. AR£ !N NAND �.. ,,, WALNUT CREEK, CALIFORNIA 94596 <br /> PROCEDURE ENGINEERS INC. p(ohibitcd, R�coR� 1�ftAWING PHONE: 925-933-0578 FAX: 925-933-0588 OWN. BY. M.L.C. DRAWING E-2 <br /> NOT TO SCALE CHKD, BY:H.A.(PEf 9034) SHEET OF <br />