Laserfiche WebLink
SWRCB, January 2002 <br />6. PIPING SUMP TESTING <br />Page of <br />Test Method Developed By: ❑ Sump Manufacturer ; Industry Standard X Professional Engineer <br />i.. Other (Specify) <br />Test Method Used: _ Pressure , Vacuum X Hydrostatic <br />1_: Other (Spec) <br />Test Equipment Used: Caldwell Level Change Indicator <br />Equipment Resolution: .002 <br />�i �; «• Sump # 1-87-M <br />Sump Diameter: 42" <br />Sump # 2-87-S <br />Sump # 3 -Diesel <br />Sump # <br />42" <br />46" Hexagon <br />Sump Depth: <br />40" <br />41" <br />41 't/z" <br />Sump Material: <br />Fiberglass <br />Fiberglass <br />Fiberglass <br />Height from Tank Top to Top of <br />Highest Piping Penetration: <br />16" <br />10" <br />21 %z" <br />Height from Tank Top to Lowest <br />Electrical Penetration: <br />10" <br />10" <br />18" <br />Condition of sump prior to testing: <br />Dry <br />Dry <br />Dry <br />Portion of Sump Tested' <br />Water Line 18" <br />Water Line 13" <br />Water Level 23 %z" <br />Does turbine shut down when <br />sump sensor detects liquid (both <br />product and water)?* <br />Yes <br />Yes <br />Yes <br />Turbine shutdown response time <br />Not Alarmed <br />Not Alarmed <br />Not Alarmed <br />Is system programmed for fail-safe <br />shutdown?' <br />Yes <br />Yes <br />Yes <br />Was fail-safe verified to be <br />operational?* <br />No <br />No <br />No <br />Wait time between applying water <br />and starting test: <br />5 Minutes <br />5 Minutes <br />5 Minutes <br />Test Start Time: <br />11:17 <br />11:12 <br />11:50 <br />Initial Reading (Ri): <br />.001 <br />.001 <br />.001 <br />Test End Time: <br />11:47 <br />11:42 <br />12:20 <br />Final Reading (RF): <br />.001 <br />> .030 <br />.001 <br />Test Duration: <br />30 Minutes <br />30 Minutes <br />30 Minutes <br />Change in Reading (RF -RI): <br />0 <br />> .030 <br />0 <br />Pass/Fail Threshold or Criteria: <br />.005/30 Minutes <br />.005/30 Minutes <br />.005/30 Minutes <br />Test Result: <br />Pass <br />*Fail <br />Pass <br />Was sensor removed for testing? <br />Yes <br />Yes <br />Yes <br />Was sensor properly replaced and <br />verified functional after testing? <br />Yes <br />Yes <br />Yes <br />COMMIAS — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />*Piping Sump #2 Regular 87 Siphon will not maintain test level and has a gross loss of >.030 in 5 minutes <br />I reset the Level Change Indicator 3 times to verify consistent loss rate. <br />Found Electrical Conduit Penetration on South wall for the Cathodic Protection Wiring to be breached. <br />Recommend a repair contractor be consulted. <br />' If the entire depth of the sump is not tested, specify how much was tested. If the answer to any of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire sump must be tested. (See SWRCB LG -160) <br />