OPEN CLASS II VIOLATION # 711 <br /> CFR 112.8 (c)(6) Failed to perform scheduled tank tests or <br /> inspections by appropriately qualified personnel. <br /> The 10,000 gallon tank was not tested on schedule by qualified personnel. <br /> The SPCC plan calls for formal STI SP-00 inspections by a certified SP-001 <br /> inspector every 10 years. The tank is older than ten years and a formal <br /> inspection has not been conducted. Also, the inspection/testing of the onsite <br /> mobile refueler must be addressed in the SPCC plan. Immediately conduct <br /> the necessary testing and submit a copy of the test results to the EHD and <br /> address testing/inspections for all qualified tanks per industry standards or <br /> provide equivalence as allowed by CFR 112.7(a)(2). <br /> ................................................................................................................................................... <br /> Northwest Pipe Company <br />