Laserfiche WebLink
SAN J O A Q U I N Environmental Health Department <br /> CQUNTY <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> ARCO 06080 85 E LOUISE AVE. LATHROP January 22, 2019 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 309 CCR 2636(f)(1) Monitoring in sump/UDC failed to activate an audible and visual alarm or stop the flow product. <br /> The 87 STP liquid sensor failed when tested. The continuous monitoring system shall be maintained to detect the <br /> entry of the liquid or vapor phase of the hazardous substance stored in the primary containment into the secondary <br /> containment and to detect water intrusion into the secondary containment. The technician onsite indicated that the <br /> sensor was stuck, he manipulated the sensor until it was moving freely and retested the sensor with passing results. <br /> This was corrected at the time of inspection. <br /> This is a minor violation. <br /> 316 HSC 25290.1(c3), 25290.2(c3) Secondary containment not constructed to prevent water intrusion (after Jul 2003). <br /> The following VPH components were missing at the time of inspection: clamps for the installed shroud boots on all <br /> 87-octane spill containers, spill container shroud boots and clamps on the 91-octane and the diesel spill containers. <br /> Secondary containment shall be constructed to prevent any water intrusion into the system by precipitation, <br /> infiltration, or surface runoff. Immediately contact a properly licensed, trained, and certified contractor to address <br /> these missing secondary containment system components, submit proof of correction to the EHD. <br /> This is a repeat violation, Class II. <br /> Overall Inspection Comments: <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, by February 21, 2019. <br /> Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate ($152). To schedule an <br /> appointment, please call (209) 468-3420. <br /> AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br /> THIS FACILITY BACK INTO COMPLIANCE. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: Date: January 22, 2019 Inspector: Inspector Phone: <br /> Printed Name and Title: ELENA MANZO, Lead Senior REHS (209) 953-7699 <br /> � I <br /> yadira padilla, casher <br /> FA0003635 PR0231656 SCO01 01/22/2019 <br /> EHD 23-01 Rev.09/28/2018 Page 5 of 5 Underground Storage Tank Program OR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />