Laserfiche WebLink
O ANCHORING TANKS <br /> Concrete Base <br /> Tanks must be anchored in locations where water could <br /> enter the hole. Anchor points must be located less than 5.5 feet (1.7 <br /> - ' meters)from the tank centerline on 10 foot(3.2 meters) <br /> FRP HOLD DOWN STRAPS diameter tanks, 4.5 <br /> feet (1.4 meters) on 8 <br /> Xerxes Century-Cast fiberglass preshaped FRP straps foot (2.5 meters) di- <br /> are available when a tank must be anchored. Tanks ameter tanks, 3.5 feet <br /> should be anchored in locations with high water tables, (1.1 meters) on 6 foot <br /> or in installations where water could enter the hole. (1.9 meters) diameter <br /> Nominal Tank tanks, 2.5 feet (0.8 <br /> Tank Size O.D./Dia. No.of Straps meters) on 4 foot (1.3 <br /> 550; 1,000 4' 2 <br /> 2,000;4,000 6' 2 meters) tanks. <br /> 6,000 6' 4 The anchors must be <br /> s,000 8' 2 fflliii� <br /> 8,000-12,000 8' 4 secured in concrete '12 oeo <br /> 10,000-15,000 10' 4 and attached to the ilia <br /> 20,000 10' 6 <br /> hold-down straps with <br /> CAUTION: All hold-down straps must be uniformly wire cable(see table II) using at least three cable clamps. <br /> snug. The load will be equally distributed when all <br /> straps are uniformly snug over the tank. Straps must TABLE II <br /> be tightened until they are snug, but cause no de- REQUIRED WIRE ROPE/TURNBUCKLE SIZE <br /> flection b checking tank diameter ick Wire Rope <br /> yecganameer wa gauge stick Diameter 1/2"(13mm) <br /> before and after snugging straps. Maximum allow- Tensile strength 12,500 lbs.(5670 kg) <br /> able deflection is 1/2 inch for 4 foot,3/4 inch for 6 foot, Turnbuckle Diameter <br /> Hook Type 11/4"(32mm) <br /> 11/4 inch for 8 foot and 11/2 inch for 10 foot diameter Eye Type 3/4"(lsmm) <br /> tanks. All tanks must be measured to determine <br /> vertical deflection before and after installation. Deadman <br /> CAUTION: Place straps only on locations designa- A deadman must be a concrete beam with a total length <br /> ted by arrows (►4) stenciled on tank. of 12 inches (30cm) greater than the total length of the <br /> tank. See table below for deadman dimensions for each <br /> Top Cable/Clamp Method tank size. <br /> An alternative method is to clamp the cables at the top TABLE III <br /> of the tank. In this REQUIRED <br /> method, triple clamp a DEADMAN DIMENSIONS <br /> cable to each end of the it TANK DEADMAN <br /> SIZE SIZE <br /> strap, thread each ca- 4 n.(1.2 m) 6••x 6 <br /> ble around the anchor (15 cm x 15 cm) <br /> or dle (30 <br /> eadman, and tri 6ft.(,.Bm) x,2 <br /> p / (30 cm x 30 cm) <br /> clamp the cable ends at CABLE 8 ft.(2.4 m) 12 x,2" <br /> the top of the tank. The ME Ho (30 cm x 30 cm) <br /> o 10 M.(3.0 m) 18••x 24" <br /> cable must rest on the <br /> (46 cm x 61 cm) <br /> top of the hold-down <br /> '� ° <br /> strap between the ti, Lay the deadman <br /> guides provided. Ad- parallel to the tank, <br /> just tension on cables not more than 5.5 1 = " <br /> evenly. feet(1.7 meters)from <br /> the centerline of the <br /> 10 foot (3.2 meters) diameter tanks, 4.5 feet (1.4 me- <br /> ters)on 8 foot(2.5 meters)diameter tanks,3.5 feet(1.1 <br /> meters) on 6 foot (1.9 meters) diameter tank, 2.5 feet <br /> (0.8 meter) from centerline of 4 foot (1.3 meters) tank. <br /> Position each hold-down strap so it will be centered on <br /> the locations designated by arrows (PA) stenciled on <br /> the tank. Fasten the wire cable to the deadman with at <br /> least three clamps. Connect the cable and strap with a <br /> turnbuckle, then tighten uniformly with other straps. <br />