Laserfiche WebLink
30 January 2004 <br /> AGE-NC Project No 96-0232 <br /> Page 6 of 15 <br /> Laboratory analysis ofR-2 grab water samples collected during the above monthlymomtormg events <br /> reported turbidity values at concentrations between 0 1 and 3 7 nephelometric turbidity units <br /> (NTUs), a TDS value of 571 mg/1 was reported on 09 December 2003 Analytical results are <br /> summarized In Table 2, field measurements and laboratory reports are in Appendix C <br /> 2 7 MASS-VOLUME REMOVAL CALCULATIONS <br /> Based on effluent flow meter observations(Appendix A,Table 8),approximately 1,109,431 gallons <br /> of MTBE-impacted water were treated during the fourth quarter 2003, a total volurne of <br /> approximately 23,535,076 gallons of MTBE-impacted water has been treated at the site since the <br /> start-up period in November 2000 <br /> The volume of extracted water between 15 September and 06 November 2003 was equal to 520,191 <br /> gallons, which equates to a mass of 4,336,832 pounds of processed water Multiplying the average <br /> MTBE concentration (assumed to be 24 5 µg/1 based on the average of the September and the <br /> November 2003 influent grab water samples) by the pounds of extracted MTBE-impacted ground <br /> water yields approximately 0 11 pounds of MTBE removed from MTBE-impacted ground water <br /> during this period(Appendix D) <br /> The volume of extracted water between 06 November and 19 November 2003 was equal to 231,641 <br /> gallons,which equates to amass of 1,931,191 pounds of processed water Multiplying the average <br /> MTBE concentration (assumed to be 29 �ig/l based on the average of the 06 November and the 19 <br /> November 2003 influent grab water samples)by the pounds of extracted MTBE-impacted ground <br /> water yields approximately 0 06 pounds of MTBE removed from MTBE-impacted ground water <br /> during this period (Appendix D) <br /> The volume of extracted water between 19 November and 09 December 2003 was equal to 171,423 <br /> gallons,which equates to a mass of 1,429,154 pounds of processed water Multiplying the average <br /> MTBE concentration (assumed to be 23 5 gg/1 based on the average of the November and the <br /> December 2003 Influent grab water samples) by the pounds of extracted MTBE-impacted ground <br /> water yields approximately 0 07 pounds of MTBE removed from MTBE-impacted ground water <br /> during this period (Appendix D) <br /> During the fourth quarter 2003, an estimated 0 24 pounds of MTBE was extracted from ground <br /> water,to date,the groundwater treatment system has removed a total of approximately 12 53 pounds <br /> of MTBE from extracted ground water(Table 8) Fourth quarter 2003 mass-volume calculations of <br /> MTBE-impacted ground water extracted from the ground water pump-and-treat system are presented <br /> in Appendix D Plots of cumulative ground water pump and treat mass removal trends and influent <br /> ground water MTBE concentrations versus time are In Appendix E <br /> Advanced GeoEnwronmental,Inc <br />