Laserfiche WebLink
D) Conduit Adhesive Injection <br />Your galvanized conduit must be lightly sanded, clean and dry. <br />You will now seal your conduit to the F -Series fitting. <br />YOUR SUMPS AND FITTINGS MUST BE COMPLETELY DRY! <br />USE SMITH TM ADHESIVE # 7069 or 8069 <br />or AMERONTM PSX-20 8oz ONLY <br />Follow your pipe manufacturers adhesive Instructions to mix and apply your <br />adhesive. DO NOT MIX MORE THAN ONE KIT AT A TIME. SEE PAGE 4 FOR KIT TYPES. <br />IMPORTANT <br />YOU MUST PURGE THE AIR FROM THE <br />TIP OF THE ADHESIVE SYRINGE <br />THERE CAN NOT BE MOISTURE IN THE ADHESIVE <br />CHANNELS OF THE FITTING. DRY YOUR FITTINGS <br />WITH AIR. USE CAUTION WHEN USING ELECTRIC <br />DRYERS OR OTHER AIR SOURCE. <br />ADHESIVE JOINT CHART <br />SEE PAGE 4 FOR KIT TYPES <br />3/4" Conduit - 15 ml Adhesive <br />1" Conduit - 20 ml Adhesive <br />NO AIR! <br />DO NOT <br />COMPLETELY <br />FILL SYRINGE <br />HINT! <br />LOAD YOUR <br />SYRINGE BY <br />PLACING TIP IN THE <br />CAN OF MIXED <br />ADHESIVE AND <br />DRAWING IT UP <br />DIRECTLY. THIS <br />METHOD IS NEAT <br />AND CLEAN. <br />USE SMITH TM ADHESIVE # 7069 or 8069 <br />or AMERONTM PSX-20 8oz ONLY <br />9 ii -F -Series -1 X -SS -11 A <br />