Laserfiche WebLink
.y Tanknology <br /> Executive Summary <br /> Republic Services Manteca <br /> Forward Landfill 9999 S.Austin Road <br /> Manteca, CA 95366. <br /> • Tank I :Are the Tanks Grounded And/Or Bonded Properly?-Ground tanks per NFPA 780 or other accepted <br /> industry standard. <br /> • Tank I :Emergency Contact Numbers Posted As Required?- Emergency plan is required and should include <br /> posting of emergency contact numbers. <br /> • Tank I :Filling Procedures Posted At Fill As Required?-Install signage at the fill point to document filling <br /> procedures. <br /> • Tank I :Fire Valve installed?- Install a fire valve on product transfer piping through which liquid could Flow through <br /> gravity. <br /> • Tank I :NFPA Signage-Faded. <br /> • Tank I :Normal Ven!Properly Sized?- Per NFPA 30 2015 21.4.3.3 Normal vents shall be sized in accordance <br /> with either API Standard 2000,Venting Atmospheric and Low-Pressure Storage Tanks,or another approved <br /> standard.Alternatively,the normal vent shall be at least as large as the largest filling or withdrawal connection,but in <br /> no case shall it he less than I?in.(3.2 em)nominal inside diameter. <br /> • Tank I :Stairways-Handrails-Platforms-Ladders-Damage <br /> • Tank I : Tank Capacity And Tank ID Posted On The Tank As Required?-Clearly label tank with capacity and <br /> ID. <br /> • Tank I : Tank Support Condition- Paint failure and corrosion. <br /> Estimated Repair Total,ifapplicable: <br />