AST SP001 ANNUAL INSPECTION <br /> General Inspection Information: <br /> (36 months from inspection <br /> Inspection Dale: 112412019 Retain Until Data: 11242022 dale) <br /> Pnor Inspection Date: Unavailable Inspector Name: PhBp Thk4 <br /> Tanks Inspected(ID6's):Gealm UNLEADED <br /> Inspection Guidance: <br /> D For equipment not included in this standard,follow the manufacturer recommended inspection/testing schedules and <br /> procedures. <br /> D The periodic AST Inspection is intended for monitoring the external AST condition and its containment structure.This visual <br /> inspection does not require a Certified Inspector. It shall be performed by an owner's inspector who is familiar with the site <br /> and can identify changes and developing problems. <br /> • Remove promptly upon discovery standing water or liquid in the primary tank,secondary containment area,interstice,or <br /> spill container. Before discharge to the environment,inspect the liquid for regulated products or other contaminants and <br /> disposed of it properly. <br /> r In order to comply with EPA SPCC(Spill Prevention,Control and Countermeasure) rules, a facility must regularly test liquid <br /> level sensing devices to ensure proper operation(40 CFR 112.8(c)(8)(v)). <br /> Non-conforming items important to tank or containment integrity require evaluation by an engineer experienced in AST <br /> design,a Certified Inspector,or a tank manufacturer who will determine the corrective action. Note the non-conformance and <br /> corresponding corrective action in the comment section. <br /> ➢ Retain the completed checklists for 36 months. <br /> ➢ Complete this checklist on an annual basis supplemental to the owner monthly-performed inspection checklists. <br /> ➢ Note: If a change has occurred to the tank system or containment that may affect the SPCC plan,the condition <br /> should be evaluated against the current plan requirement by a Professional Engineer knowledgeable in SPCC <br /> development and implementation. <br /> Item I Task Status <br /> 1.0 Tank Containment <br /> 1.1 Containment structure Ia structure free of, r Yes r No r N/A <br /> • Holes or cracks in containment wall or floor r Yes r No r N/A <br /> • Washout r Yes r No r N/A <br /> • Liner degradation 171 Yes rNo r-N/A <br /> • Corrosion <br /> • Leakage r Yes r No r N/A <br /> • Paint failure r Yes r No r N/A <br /> • Tank settling I,Yes r No r N/A <br /> Comments: <br /> 2.0 Tank Foundation and Sul ports <br /> 2.1 Foundation No observed settlement or foundation washout? r Yes r No <br /> 2.2 Concrete pad or ring wall No visible cracking or spelling? r Yes r No r N/A <br /> 2.3 Supports No visible corrosion,paint failure,etc.? r Yes r No r N/A <br /> 2.4 Water drainage Water drainage away from tank? r Yes r No r N/A <br /> 2.5 Tank grounding Strap secured and in good condition? r Yes r No r N/A <br /> If intrinsically ground, please note in comments. <br /> Comments: <br /> WD: 6703239 SEPTEiMER2016 <br />