Laserfiche WebLink
Safeway, 1987 W 11t reet, Tracy CA <br />c. A valid, current certificate of training from the manufacturer(s) of the <br />component(s) being tested, repaired, or serviced; <br />And <br />d. Each person installing or testing any component must hold a certificate of <br />training from the manufacturer of that component. <br />Call Michelle Henry to arrange the following inspections (a 48 hour notice is <br />required): <br />- Visual inspection of the capped vapor recovery line. <br />- Visual inspection to ensure the new dispensers fit the existing footprint of the UDCs. <br />- Secondary containment testing of all product lines after installation of new dispensers. <br />- Secondary containment testing of the diesel fill sump after concrete has been poured. <br />- Secondary containment testing of the diesel UST after concrete has been poured. <br />- Inspection of the ATG probes to verify the 90% tank volume shutoff and audio/visual <br />alarm. <br />- Verification that the Diesel PLLD will detect a leak of 3 gallons per hour at 10 PSI. <br />Mi elle F�ernry, REHS <br />niorgistered Environmental Health Specialist <br />20 953-7699 <br />09) 468-3433 Fax <br />mhenry@sjcehd.com <br />c: Stan Olea <br />C/o Safeway. Inc. <br />5918 Stoneridge Mall Road <br />Pleasanton CA 94588 <br />Page 2of2 <br />