Laserfiche WebLink
JAR -20-2009 09:33 Service Station Systems 408 938 8888 P.04 <br />TANK ANNITLAR TFNTING <br />Test Method Developed By: ❑ Tank Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Specify) <br />Test Method Used: ❑ Pressure 0 Vacuum ❑ Hydrostatic <br />p Other (Specify) <br />Test Equipment Used: Test plugs, vernturi pump and gauges Equipment Resolution: 0.5% of span <br />Tank # 87 Tank # 89/91 <br />Is Tank Exempt From Testing?' [IYes ® No ❑Yes ® No <br />Tank Capacity: <br />20k 20k <br />Tank Material: <br />Steel Steel <br />Tank Manufacturer: <br />Modern welding Modern welding <br />Product Stored: <br />Gasoline Gasoline <br />Wait time between applying <br />pressure/vacuum/water and <br />10 min. 10 min <br />starting test: <br />Test Start Time: <br />8:30 am 9:00 am <br />Initial Reading (RO: <br />7" 7" <br />Test End Time: <br />9:30 am 10:00 am <br />Final Reading (RF): <br />7" 7" <br />Test Duration: <br />1. hour 1 hour <br />Change in Reading (Rr RO: <br />None None <br />Pass/Fail Threshold or Criteria: <br />No detectable loss No detectable loss <br />Test Result: <br />© Pass )rail ® Pass rail <br />Was sensor removed for testing? <br />0 Yes ❑ No ❑ NA ® Yes ❑ No a NA <br />Was sensor properly replaced and <br />®Yes p No LI NA ®Yes p No ❑ NA <br />verified functional after testing? <br />Comments — (include information on re airs made prior to testing, and recommended follow -u or failed tests) <br />"Sensor functionality was not confirmed. This procedure is not part of the Secondary Containment testing scope of work". <br />Seoondaxy co+atijament systems where the contimiam monitoring autamadcany monitors Troth the primary and secandarq <br />containment, stuff as systems that are hydrostatically monitored or under consmarcacuam; ane exempt fC m periodic containment <br />testing. {Ca itr+rn4 Cede of Regulations, Title 23, Section 2637(a)(6)1 <br />