Laserfiche WebLink
JAN -20-2009 09:34 Service Station Systems 408 938 8888 P.08 <br />S. UNDER -DISPENSER CONTAINMENT (UDC) TESTING <br />'fest Method Developed By: ❑ UDC Manufacturer Z Industry Standard ❑ Professional Engineer <br />❑ Other (Specify) <br />Test Method Used: p Pressure ❑ Vacuum U Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used: Incon Sump Tester <br />UDC #1/2 UDC #3/4 <br />Equipment Resolution: <br />UDC #5/6 UDC # 7/8 <br />UDC Manufacturer <br />Western fiberglass <br />Western fiberglass <br />Westum Fiberglass <br />Western fiberglass <br />UDC: Material: <br />Fiberglass <br />Fiberglass <br />Fiberglass <br />Fiberglass <br />UDC De the <br />31" <br />31" <br />31" <br />31" <br />Height from UDC Bottom to Top <br />of Highest Piping Penetration: <br />12" <br />12" <br />12" <br />12" <br />Height from UDC Bottom to <br />Lowest Electrical Penetration: <br />13" <br />13" <br />13" <br />13" <br />Condition of UDC prior to <br />testing: <br />Good <br />Good <br />Good <br />Good <br />Portion of UDC Tested <br />2" above eipinp <br />1 2" above piping <br />2" above piping <br />2" above piping <br />Does turbine shut down when <br />UDC sensor detects liquid (both <br />product and water)?' <br />❑ Yes ❑ No UNA <br />❑ Yes ❑ No UNA <br />❑ Yes p No UNA <br />0 Yes ❑ No ® NA <br />Turbine shutdown response time <br />N/A <br />N/A <br />N/A <br />N/A <br />Is system programmed for fail- <br />safe shutdown?. <br />❑ Yes El ® NA <br />❑ Yes ❑ No ®NA <br />[IYes [INo UNA <br />❑ Yes ❑ No ® NA <br />Was fail-safe verified to be <br />operational?* <br />p Yes ❑ No ® NA <br />❑ Yes ❑ No ®NA <br />❑ Yes El No UNA <br />[1 Yes ❑ No ® NA <br />Wait time between applying <br />pressure/vacuuni/water and <br />starting test <br />30 minutes <br />30 minutes <br />30 minutes <br />30 minutes <br />Test Start Time: <br />3:58 pm <br />4:17 pni <br />3:58 2m <br />3:58 pm <br />Initial Reading (R,): <br />2,6946 <br />2.4603 <br />4,4871 <br />2.6771 <br />Test End Time: <br />4.13 pm <br />4:32 pm <br />4:13 2m <br />4:13 pm <br />Final Reading (RF).. <br />2.6940 <br />2.4483 <br />4.4873 <br />2.6778 <br />Test Duration: <br />15 min. <br />15 min. <br />15 min. <br />15 min. <br />Chane in Reading (RF -R,): <br />-0.0006 <br />-0.0120 <br />+0,0002 <br />+0.0007 <br />Pass/Fail Threshold or Criteria: <br />+/- 0.002" <br />+/- 0.002" <br />+/- 0.002" <br />+/- 0.002" <br />Test Result: <br />® Pass Fail <br />Pass 0 Fail <br />© Pass Fail <br />® Pass Fail <br />Was sensor removed for testing? <br />® Yes C3 No ❑ NA <br />® Yes ❑ No ❑ NA <br />I E Yes ❑ No ❑ NA <br />® Yes ❑ No Q NA <br />Was sensor properly replaced and <br />verified functional after testing? <br />® Yes ❑ No ❑ NA <br />Yes 0 No ❑ NA <br />0 Yes ❑ No ❑ NA <br />® Yes ❑ No ❑ NA <br />Comments — (include in ormatiort on repairs Hume prior to testing, and reconzmerzded.follow-u for, failed tests) <br />"Sensor functionality was not confirmed. This procedure is not part of the Secondary Containment testing scope of work". <br />43/4 failed. Tested twice still leaking. Boot were tine <br />If age etira r{enthgf t1 L1 ic._noLiestclLsnecifv how much was tested, if the answer to any of the questions indicated with an <br />ast—kk(*) is."NO" or "NA", the entire UDC tnustbetestM (Sw_SWRC:RLGA60) <br />