Laserfiche WebLink
JAN -20-2009 09:34 Service Station Systems 408 938 8888 P.09 <br />9. UNDER -DISPENSER CONTAINMENT (UI)Q TESTING <br />Test Method Developed By: ❑ UDC Manufacturer 0 Industry Standard ❑ Professional Engineer <br />❑ Other (Specify) <br />Test Method Used: ❑ Pressure ❑ Vacuum ® Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used: Incon Sump <br />Tester <br />UDC # 9/10 UDC # 11/12 <br />Equipment Resolution: +/- 0.002" <br />UDC # 13/14 UDC # 15/16 <br />UDC Manufacturer: <br />Wcstcm fiberglass <br />Western fiberglass <br />Western fiberglass <br />Westem fiberglass <br />UDC Material: <br />Fiberglass <br />Fiberglass <br />Fiberglass <br />Fiber lass <br />UDC Depth: <br />31" <br />31" <br />31" <br />31" <br />Height from UDC Bottom to Top <br />of Highest Piping Penetration: <br />121' <br />12" <br />12" <br />12" <br />Height from UDC Bottom to <br />Lowest Electrical Penetration: <br />13" <br />13" <br />13" <br />13" <br />Condition of UDC prior to <br />testing. <br />Good <br />Good <br />Good <br />Good <br />Portion of UDC Tested <br />2" above piping <br />2" above piping <br />2" above piping <br />2" above pieftig <br />Does turbine shut down when <br />UDC sensor detects liquid (both <br />product and water)? <br />❑ Yes ❑ No ® NA <br />p Yes ❑ No ®NA <br />❑ Yes ❑ No ®NA <br />❑ Yes ❑ No ®NA <br />Turbine shutdown response time <br />N/A <br />N/A <br />N/A <br />N/A <br />Is system programmed for fail- <br />safe shutdown? <br />❑ Yes ❑ No ® NA <br />❑ Yes C) No ®NA <br />❑ Yes ❑ No ®NA <br />El Yes ❑ No ®NA <br />Was fail-safe verified to be <br />operational?* <br />❑ Yes ❑ No ® NA <br />❑ Yes ❑ No ®NA <br />❑ Yes ❑ No ®NA <br />❑ Yes ❑ No ®NA <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test <br />30 minutes <br />30 minutes <br />30 minutes <br />30 minutes <br />Test Start Time: <br />2.45 pm <br />2:45 pm <br />1:47_pin <br />1:47 2m <br />Initial Reading (Ri): <br />2.8172, <br />32432 <br />0.3136 <br />3.1080 <br />Test End Time: <br />3:00 prn <br />3:00 pm <br />2:02 pm <br />2:02 Rm <br />Final Reading (RF): <br />2.8161 <br />3.2432 <br />0.3142 <br />3.1083 <br />Test Duration: <br />15 min. <br />15 min. <br />15 min. <br />15 min. <br />Change in Reading (RF -R,): <br />-0.0011 <br />None <br />x-0.0006 <br />+0.0003 <br />Pass/Fail Threshold or Criteria: <br />+/- 0.002" <br />+/- 0.002" <br />4-0.0021, <br />+/- 0.002" <br />Test Result: <br />91 Pass Fail <br />0 Pass Fail <br />® Pass Fail <br />0 Pass Fail <br />Was sensor removed for testing? <br />f Yes ❑ .No ❑ NA <br />0 Yes ❑ No ❑ NA <br />®Yes ❑ No ❑ NA <br />® Yes p No ❑ NA <br />Was sensor properly replaced and <br />verified functional after testing? <br />® Yes ❑ No ❑ NA <br />® Yes ❑ No ❑ NA <br />® Yes ❑ No ❑ NA <br />® Yes ❑ No El NA <br />Comments — (include inf2mwtiun on repairs made prior to testing, and recommended.follow-up for ailed tests) <br />"Sensor functionality was not confirmed. This procedure is not part of the Secondary Containment testing scope of work". <br />t llfe entire depth of the UDC: is not tested.- specify how much was tested. If the answwto any of the questions indicated with an <br />nmpgk M is "Ng' or "Nk', the entire UDC must be tested- (See SWRCB LG -160) <br />