RECEIVED <br />OCT 2 0 2017 <br />TANK ANNULAR TESTING r'NVlPnKkAPmTei WCA►TU <br />Test Method Developed By: [—]Tank Manufacturer✓❑Industry Standard ❑ Profess''i5 M!111 5RWES <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure ❑✓ Vacuum ❑ Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used: Test plugs, venturi pump and gauges <br />Equipment Resolution: 0.5% inHg <br />1'anl: # 87 Tank # 91 / Diesel Tank # T'ank # <br />Is Tank Exempt From Testing'? <br />Yes ❑✓ No <br />❑Yes ✓❑No <br />❑Yes ❑No <br />[]Yes ❑No <br />Tank Capacity: <br />20k <br />20k <br />Tank Material: <br />Steel <br />Steel <br />Tank Manufacturer: <br />Modern Welding <br />Modern Welding <br />Product stored: <br />Gasoline <br />Gasoline/ Diesel <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />10 Minutes <br />10 Minutes <br />10 Minutes <br />10 Minutes <br />Test Start Time: <br />7:45AM <br />8:15AM <br />Initial Reading (Rl): <br />7 inHg <br />7 inHg <br />inHg <br />inHg <br />Test End Time: <br />8:45AM <br />9:15AM <br />Final Reading (RF): <br />7 inHg <br />7 inHg <br />inHg <br />inHg <br />Test Duration: <br />1 Hour <br />1 Hour <br />1 Hour <br />1 Hour <br />Change in Reading (RF -R►): <br />0 <br />0 <br />Pass/Fail Threshold or Criteria: <br />0 <br />0 <br />0 <br />0 <br />Test Result: <br />✓❑ Pass ❑ Fail <br />❑✓ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />Was sensor removed for testing? <br />✓❑Yes []No ❑NA <br />❑✓ Yes []No ❑NA <br />❑Yes ❑No ❑NA <br />[_—]Yes []No ❑NA <br />Was sensor properly replaced and <br />verified functional after testin�z? <br />❑✓ Yes []No❑NA <br />✓❑Yes []No❑NA <br />❑Yes ❑No ❑NA <br />[]Yes[]No❑NA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />"Sensor functionality was not confirmed. This procedure is not part of the Secondary Containment <br />testing scope of work". <br />' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br />containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment <br />testing. {California Code of Regulations, Title 23, Section 2637(a)(6)) <br />