Laserfiche WebLink
UNDER -DISPENSER CONTAINMENT (UDQ TESTING <br />Test Method Developed By: ❑ UDC Manufacturer 0 Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure ❑ Vacuum ® Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: Incon sump rester Equipment Resolution: +/-0.002 Inches <br />9/10 UDC # 11/12 UDC # 13/14 UDC # 15/16 <br />UDC Manufacturer: Western Fiberglass Western Fiberglass Western Fiberglass Western Fiberglass <br />UDC Material: <br />Fiberglass <br />Fiberglass <br />Fiberglass <br />Fiberglass <br />UDC Depth: <br />31" <br />31" <br />31" <br />31" <br />Height from UDC Bottom to Top <br />of Highest Piping Penetration: <br />5" <br />5" <br />5" <br />5" <br />Height from UDC Bottom to <br />Lowest Electrical Penetration: <br />10" <br />10" <br />10" <br />10" <br />Condition of UDC prior to <br />testing: <br />Good <br />Good <br />Good <br />Good <br />Portion of UDC Tested' <br />2" Above Piping <br />2" Above Piping <br />2" Above Piping <br />2" Above Piping <br />Does turbine shut down when <br />UDC sensor detects liquid (both <br />N/A <br />N/A <br />N/A <br />N/A <br />product and water)?* <br />Turbine shutdown response time <br />N/AN/A <br />N/A <br />N/A <br />N/A <br />Is system programmed for fail- <br />` <br />❑Yes E] No m NA <br />E] Yes E] No p NA <br />❑ Yes ❑ No [Z] NA <br />E] Yes E] No p NA <br />safe shutdown? <br />Was fail-safe verified to be <br />operational?* <br />❑ yes El No p NA <br />El Yes El No El NA <br />❑ Yes El No p NA <br />El Yes ❑ No p NA <br />Wait time between applying <br />pressure/vacuum/water and <br />30 Minutes <br />30 Minutes <br />30 Minutes <br />30 Minutes <br />starting test <br />Test Start Time: <br />Initial Reading (RI): <br />Inches <br />Inches <br />Inches <br />Inches <br />Test End Time: <br />Final Reading (RF): <br />Inches <br />Inches <br />Inches <br />Inches <br />Test Duration: <br />Change in Reading (RF -RI): <br />Pass/Fail Threshold or Criteria: <br />0.002 <br />0.002 <br />0.002 <br />0.002 <br />Test Result: <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />Was sensor removed for testing? <br />ED] es ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />Was sensor properly replaced and <br />❑ Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />verified functional after testing? <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />UDC 9/10, 11/12, 13/14, 15/16 Visually failed due to jumper lines. <br />"Sensor functionality was not confirmed. This procedure is not part of the Secondary Containment <br />testing scope of work". <br />