Laserfiche WebLink
San Joaquin County <br /> Environmental Health Department <br /> 1868 East Hazelton Avenue, Stockton, California 95205-6232 <br /> Telephone: (209)468-3420 Fax; (209)468-3433 Web:www.s'gov.org/ehd <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> SJ CO PUBLIC WORKS CORP YARD* 1 1810 E HAZELTON AVE, STOCKTON March 08, 2019 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 209 CCR 2716(a-e) Failure to conduct the designated UST operator visual inspection at least once every 30 days. <br /> -A designated operator inspection was performed on 12/18/18 and the next inspection was performed on 1/22/19, 35 <br /> days later. <br /> -A designated operator inspection was due on 2/16/19 and was performed on 2/19/19, 3 days late. <br /> The designated operator visual inspections shall be conducted within 30 days or less of the previous inspection. <br /> Ensure that all designated operator inspections are performed within the required time frames. <br /> The designated operator failed to check and note all required items on the visual inspection reports. <br /> -The March 2018 inspection report included an incorrect monitoring certification test date. <br /> -The 11/8/18 L2 (87 annular) high liquid alarm was not documented. <br /> -Section V&VI were left blank in the 10/29/18, 12/18/18, and 2/19/19 inspection reports. <br /> -Section V&VI were filled out by the designated operator instead of the owner/operator in the 11/20/18 and 1/22/19 <br /> inspection reports. <br /> During the visual inspection, the designated operator shall check that all required testing and maintenance for the <br /> UST system have been completed and shall check all required items on the report. Ensure that designated <br /> operators performing visual inspections at this facility are including all of the required information on the reports. <br /> This is a minor violation. <br /> 306 CCR 2630(d) Monitoring equipment is not installed or maintained to detect a leak at the earliest opportunity. <br /> On 6/27/18 an L2 (87 annular) high liquid alarm occurred. <br /> On 7/18/18 the alarm was found by the designated operator during the monthly inspection. <br /> On 7/27/18 the alarm was stopped and corrected by the designated operator/technician. <br /> The interstitial space shall be monitored with a continuous monitoring system connected to an audible and visual <br /> alarm system. The monitoring system shall be monitored by the site in order to detect alarms at the earliest <br /> opportunity and alarms shall be responded to by the owner/operator immediately when found. Ensure the UST <br /> system is being continuously monitored and all alarms are addressed in a timely manner. <br /> This is a repeat violation, Class II. <br /> 307 CCR 2631(g), 2632(c) Monitoring system of the interstitial space of a double walled system not maintained. <br /> On 6/27/18 an L2 (87 annular) high liquid alarm occurred. <br /> On 7/18/18 the alarm was found by the designated operator during the monthly inspection. <br /> On 7/27/18 the alarm was stopped and corrected by the designated operator/technician. <br /> The interstitial space shall be monitored with a continuous monitoring system connected to an audible and visual <br /> alarm system. The monitoring system shall be monitored by the site in order to detect alarms at the earliest <br /> opportunity and alarms shall be responded to by the owner/operator immediately when found. Ensure the UST <br /> system is being continuously monitored and all alarms are addressed in a timely manner. <br /> This is a Class II violation. <br /> FA0003954 PR0231141 SCO01 03/08/2019 <br /> EHD 23-01 Rev.09/22/16 Page 4 of 6 Underground Storage Tank Program OIR <br />