Laserfiche WebLink
JUN-03-2009 09 :06 AM GETTLER—RYAN INC. 925 551 4770 P. 03 <br /> Monitoring System Certification <br /> D. Results of Testing/Servicing <br /> Software Version Installed; 329.40 <br /> Com tete the folio Ing checklist: <br /> ® Yes ❑ No* Is the audible alarm operational:' <br /> ® Yes ❑ No* Is the visual alarm operational'' <br /> ® Yes ❑ No* Were all sensors visually inspected, functionally tested. and confirmed operational? _ <br /> ® Yes ❑ No* Were all sensors installed at lowest point of secondarl containment and positioned ya that ocher equipment will <br /> not interfere with their proper operation? <br /> ❑ Yes ❑ NO If alarms are relayed to a remote monitoring station. is all communications equipment (est:.. modem) <br /> ® NIA operational'? <br /> ® Yes 0 No* For pressurized piping systems. does the turbine automatically shut down if the piping; secondary containment <br /> ❑ N/A monitoring;system detects a leak_ fails to operate. or is electrically disconnected? if yea: which sensor, initiate <br /> positive shut-down? (Check gill chin apply) ® Sump French Sensors: 0 Dispenser Containment Sensors. <br /> Did you confirm positive shut-down due to leaks and sensor failure:'disconnection? 9 Yes, 13 No, <br /> Z Yes ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device tile.. no <br /> [� N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank <br /> tillpoint(s)and operating properly? If so.at what percent of tank capacity does the alarm trigger? 90% <br /> 0 Yes* ❑ No Was any monitoring;equipment replaced" If yes, identify specific sensors, probes, or other equipment replaced <br /> and list the manufacturer name and model for all replacement parts in ScL:tion P., below. _ <br /> ❑ Yes" ❑ No Was liquid l6und inside any secondary containment;\items designed as dry•systems? (.Uheck all char apply <br /> [J Product, ❑ Water. If yes,describe causes in Section F. below, _ <br /> ❑ Yes ❑ No` Was monitoring system set-up reviewed to ensure proper settings'? Attach set up reports, if applicable <br /> ❑ Yes ❑ No* Is all monitoring,equipment operational per manufacturer's specifications? <br /> " In Section F,below.describe how and %hen these deficiencies were or will be corrected. <br /> E. Comments: t.-11 Sensor 91 Fill Sump. 87 master probe failed overfill alarm at 90% alarms at 95% need to repair <br /> and retest. OveAll ala"mat tank pad had Wbe-FepIaeed--L-4-seMSeF was40plase tested—with <br /> —VeFm+applied-feF, AleFPA bo-Feplased iAd-tested-w44-W peetof-peftitit-epplit 4EW--- <br /> Page 2 of 3 <br />