STEP 25 : INSTALL WARNING PLATE <br /> Bend the three warning plate ears down then slide the <br /> tie wrap over the warning plate ears and position warn - <br /> ing plate against riser pipe approximately 1 " below the <br /> adaptor. Tighten the tie wrap securely . The valve is <br /> now fully installed and in operating position . <br /> 0 <br /> NOTE : the warning plate includes important warn - <br /> ings, operating parameters, and listing information OP A <br /> A <br /> must be installed . p <br /> X15 <br /> u4 FO f�addadt <br /> a1• ' <br /> fo,m <br /> 0* 6 w" <br /> r <br /> Manufacturer : "OPW" <br /> Models '71 SO-4" <br /> (4" represents size) <br /> Manufacture Date, <br /> "MFG MMYY" <br /> MM= Month YY= Year <br /> Warning <br /> Plate <br /> Figure 26 " Product Identification <br /> Figure 25 <br /> STEP 26 : VALVE REMOVAL <br /> The valve can be removed for tank leak testing, inspec- <br /> tion , etc ., by removing the Rotatable Product Adaptor, <br /> the 4 " nipple, and the Jack Screw Kit . Reinstall per the <br /> above instructions . <br /> For testable models only : It is not necessary to re- <br /> move the valve to check poppet movement / function . <br /> See Page 17 for full testing details . <br /> STEP 27 : ELECTRONIC LIQUID LEVEL MONITORING <br /> If an electronic level monitor is installed , it must be cali - <br /> brated to match the top of the 71 SO valve body, which <br /> must correlate with 95 % of the actual tank capacity. <br /> 16 <br />