FEE-25-2011 15 37 Service Station Systems 408 938 8888 P.05 <br /> 5. SECONDARY PIPE TESTING <br /> iTest Method Developed By: ❑ Piping Manufacturer ® Industry Standard ❑ Professional Engineer <br /> ❑ Other(Spec0y) <br /> Test Method Used: ® Pressure p Vacuum ❑ Hydrostatic <br /> ❑ Other(Specify) <br /> Test Equipment Used: Test reducer boots,Nitrogen and gauges Equipment Resolution: 0,501,, of span <br /> Piping Run#87 1 Piping Run#89 Piping Hun#91 <br /> Pipin,Material: Fiberglass Fiberglass Fiberglass <br /> Piping Manufacturer: Smith Smith Smith <br /> Piping Diameter: 3' 3' 31. <br /> Length of Piping Run: 100, 100, 100, <br /> Product Stored: w Gasoline Gasoline Gasoline <br /> Method and location of Reducer Buotss/Fittings Reducer Boots/Fittings Reducer BootsaFittinks <br /> piping-run isolation: <br /> Wait time between applying <br /> pressure/vacuum/water and 10 minutes 10 minutes 10 minutes <br /> startinv test: _ <br /> Test Start Time: <br /> Initial Reading(R[): f <br /> Test End Time: _ <br /> ifinal Reading(Rf:): .—._.r..�__.__......_...,.._i_._.._.�_. �. .._y_.__.._.___._._.�,�,..._.. <br /> Test Duration: <br /> Change in Reading(Rr-12,): <br /> Pass/Fail Threshold or <br /> Criteria: <br /> j Test Result: 0 Pass ® Fail 0 Pass CM Fail 0 Pass I@ Fail <br /> Comments— (include information on repairs made prior to le.%1in and recommended follow-up for failed lcsls) <br /> Visual fail. All three test boots are cracked.Need 3 boots. <br /> Need(2)per 3.5 x 2.4 OSA ^ _ � - <br /> Need(l)per 3.5x2.4A <br /> Offset boots are for 89 and 91 lines <br />