Laserfiche WebLink
FEE-25-2011 15 39 Service Station Systems 408 938 8889 P. 10 <br /> i <br /> 10. SPILL/OVERFILL CONTAINMENT BOXES <br /> Facility is Not Equipped With Spill/Overfill Containment boxes E) <br /> Spill/Overfill Containment Boxes are Present,but were Not Tested ❑ <br /> Test Method Developed By: ❑ Spill Bucket Manufacturer ® Industry Standard ❑ Professional Engineer <br /> ❑ Other(Speer <br /> Test MethodUsed: ❑ Pressure p Vacuum ® Hydrostatic <br /> El Other(Specify) <br /> Test Equipment Used: Incon Sump Tester F,quipment Resolution: +/-0.002" <br /> Vapor Spill Boz#87 Vapor Spill Box#89 Vapor Spill Box#91 <br /> Bucket Diameter: 12" 12" 12" <br /> Bucket Depth: 10" 10" 10" <br /> Wait time between applying <br /> pressure/vacuum/water and 10 min. 10 min. 10 min. <br /> starting test: <br /> Test Start Time: 7:54 am 7:54 am 7:54 am <br /> Initial Reading(R,): 4.3861 5.3007 4.8116 <br /> Test End Time: 8:09 am 8:09 am 8:09 am <br /> Final Reading(Rp): 4.3865 5.3008 4.8115 <br /> Test Duration: 15 min. 15 min. 15 min. <br /> Change in Reading(RF-R,): x-0.0004 +0.0001 -0.0001 <br /> Pass/Fail Threshold or +/-0.002" +/-0.002" +/-0.002" <br /> Criteria: <br /> Test Result: El Pass ❑Fail ® Pass 0 Fail Cl Pass [] Fail <br /> Comments—(inclu(le information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> TOTAL P. 10 <br />