FEB-25-2011 15:38 Service Station Systems 408 938 8888 P.09 <br /> 9. SPILL/OVERFILL CONTAINiMENT BOXES <br /> Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ <br /> Spill/Overfill Containment Boxes are Present,but were Not Tested ❑ <br /> Test Method Developed By: ❑ Spill Bucket Manufacturer M Industry Standard ❑ Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure ❑Vacuum ® Hydrostatic <br /> ❑ Other(Sped) _ <br /> Test Equipment Used: lncon Sump'fester Equipment Resolution: +/-0.002" <br /> Fill Spill Box#87 Fill Spill Box#89 Fill Spill Box# 91 <br /> Bucket Diameter: 12" 12" 12" <br /> Bucket Depth: 101" 10" 10" <br /> -� <br /> Wait time between applying <br /> pressure/vacuum/water and I 10 min. 10 min. 10 min, <br /> starting test: I <br /> Test Start Time: 7:36 am 7:36 am 7:.36 am <br /> Initial Reading(R(): 3.0688 3-8654 3.3097 <br /> �I <br /> Test End Time: 7:51 am 7:51 aro 7:51 ani— <br /> Final <br /> mFinal Reading(RF): 3.0685 3.8648 3.3092 <br /> Test Duration: 15 min. 15 min. 15 min, I <br /> Change in Reading(RF-R,): -0.0003 -0.0006 -0.0005 <br /> Pass/Fail Threshold or <br /> +/-0.00Z" +/-0.002" +/-Q.QOZ„ <br /> Criteria: <br /> Test Result: 0 Pass 0 Fail 0 PassT 0 Fail m Pass 0 Fail <br /> Comments— (include information on repairs made prior to teslin,Z, and recommended,follow-up for failed tests) <br />