Laserfiche WebLink
RECEIVED <br /> IAN 0 8 2016 <br /> 6. PIPING SUMP TESTING 1—All 11WQNr <br /> Test Method Developed By: ❑ Sump Manufacturer ® Industry Standard ❑ PrSf�ss-o - gi8g@rr"::- l <br /> ❑ Other(Specify) <br /> Test Method Used: ❑ Pressure ❑Vacuum ® Hydrostatic <br /> ❑ Other(Specifj) <br /> Test Equipment Used: Incon Sump Tester Equipment Resolution: +/-0.002" <br /> STP Sump#87 STP Sump#91 <br /> Sump Diameter: 42" 42" <br /> Sump Depth: 63" 63" <br /> Sump Material: Fiberglass Fiberglass <br /> Height from Tank Top to Top of 1411 15" <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 26" 26„ <br /> Electrical Penetration: <br /> Condition of sump prior to testing: Good Good <br /> Portion of Sump Tested' 2"above piping 2"above piping <br /> Does turbine shut down when <br /> sump sensor detects liquid(both ❑Yes❑No ®NA []Yes❑No ®NA <br /> product and water)?* <br /> Turbine shutdown response time N/A N/A <br /> Is system programmed for fail-safe ❑Yes 0 No ®NA ❑Yes❑No ®NA <br /> shutdown?' <br /> Was fail-safe verified to be ❑Yes❑No ®NA []Yes❑No ®NA <br /> o erational?* <br /> Wait time between applying <br /> pressure/vacuum/water and starting 30 minutes 30 minutes <br /> test: <br /> Test Start Time: 12:20 pm 12:20 pm <br /> Initial Reading(R,): 4.4190 3.5786 <br /> Test End Time: 12:35 pm 12:35 pm <br /> Final Reading(RF): 4.4009 3.5772 <br /> Test Duration: 15 min. 15 min. <br /> Change in Reading(RF-R,): 0.0181 0.0014 <br /> Pass/Fail Threshold or Criteria: +/-0.002" +/-0.002" <br /> Test Result: ❑ Pass ® Fail O Pass ❑ Fail <br /> Was sensor removed for testing? ®Yes❑No ❑NA ®Yes❑No[INA <br /> Was sensor properly replaced and ®Yes❑No❑NA ®Yes❑No❑NA <br /> verified functional after testing? <br /> Comments— (include information on repairs made prior to testing, and reca?imended follow-up for failed tests) <br /> "Sensor functionality was not confirmed.This procedure is not part of the Secondary Containment testing scope of work". <br /> 87 STP Torn Test Boot. 3.5 x 2.0 over rook guard failed. <br /> if the entire depth of the sump is not tested,specify how much was tested. If the answer to as of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire sump must be tested. (See SWRCB LG-160) <br />