SWRCB, January 2002 Page 2 of 10 <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: X Tank Manufacturer X Industry Standard ❑ Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑ Pressure X Vacuum ❑Hydrostatic <br /> ❑Other(.Specify) <br /> Test Equipment Used: Vacuum pump with 0-30"hg dial gaugeI Equipment Resolution: <br /> Tank—Split 87&91 Tank- Tank- Tank- <br /> Is Tank Exempt From Testing" ❑Yes X No ❑Yes ❑No ❑Yes 17,No ❑Yes No <br /> Tank Capacity: 30,000 gallons <br /> Tank Material: Plasteel <br /> Tank Manufacturer: Eleutron <br /> Product Stored: Gasoline <br /> Wait time between applying <br /> pressure/vacuum/water and 60 minutes <br /> starting test: <br /> Test Start Time: 08:00 <br /> Initial Reading(Ri): 14" Hg <br /> Test End Time: 08:30 <br /> Final Reading(RF): 14"Hg <br /> Test Duration: 30 minutes <br /> Change in Reading(RF-R,): No change <br /> Pass/Fail Threshold or Criteria: No change=pass <br /> Test Result: X Pass ❑Fail ❑ Pass ❑Fail ❑ Pass ❑ Fail ❑ Pass ❑Fail <br /> Was sensor removed for testing? X Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> Was sensor properly replaced and X Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> verified functional after testin . <br /> Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> Test was repeated from 3-22-06 to enable store to have all components current. <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations.Title 23, Section 2637(a)(6)1 <br />