Page 2 of 7 <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: ❑Tank Manufacturer X Industry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure X Vacuum ❑Hydrostatic <br /> No annular space(single wall) ❑Other(Spec) 7�::11 <br /> 11 Test Equipment Used: Vacuum pump with 0-30"hg dial gauge Equipment Resolution: <br /> Tank#Split Tank# Tank# Tank# <br /> Ts Tank Exompt From Testing?' ❑Yes X No ❑Yes ❑No ❑Yes ❑No ❑Yes ❑No <br /> Tank Capacity: 30,000 gallons <br /> Tank Material; Plasteol <br /> Tank Manufacturer: Eleutron <br /> Product Stored: Gasoline <br /> Wait time between.applying <br /> pressure/vacuum/water and. 60 minutes <br /> starting test: <br /> Test Start Time: 11:00 am <br /> Initial.Reading(Rj): 14"hg <br /> Test End Time: 11:30 am <br /> Final Reading(Rr): 14" hg <br /> Test Duration: 30 minutes <br /> Change in.Reading(RF-Rj): No change <br /> Pass/Fail.Threshold or Criteria: No change=pass <br /> Test Result: X Pass ❑)Fail <a Pass ❑Fail ❑ Pass ❑Fail 0 Pass ❑Fail <br /> Was sensor removed for testing? X Yes ❑No 2 NA r�Yes ❑No C3 NA ❑Yes ❑No ❑NA ❑Yes 5 No [INA <br /> Was sensor properly replaced and X Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA I�Yes n No CI NA <br /> verified functional after testin ? <br /> Comments--(include information on repairs made prior to testing and recommended follow-up for failed tests) <br /> 'Secondary containment systems where the continuous monitoring automatically monitors both the primary and.secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment <br /> testing, f California Code of Regulations, Title 23.Section 2637(0(6)' <br />