Laserfiche WebLink
DEC-03-2007 11:38 Service Station Systems 408 938 8888 P.09 <br /> 9. SPILL/OVERFILL CONTAINMENT BOXES <br /> Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ <br /> Spill/Overfill Containment Boxes are Present,but were Not Tested ❑ <br /> 'rest Method Developed By: ❑Spill Bucket Manufacturer N Industry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure ❑Vacuum ®Hydrostatic <br /> ❑Other(Specify) _ <br /> Test Equipment Used: Incon Sump Tester Equipment Resolution: +/•0.002" <br /> n. a ..-' env,. •, r.. n <br /> r <br /> Vapor Spill Box#87 Fill Spill Box#87 Fill Spill Box#DSL Vapor Spill Box#91 <br /> NEIBucket Diameter: 11" 11" ll" 11" <br /> Bucket Depth: 14" 14" 14" 14" <br /> Wait time between applying <br /> pressure/vacuum/water and 10 min. 10 min. 10 min. 10 min. <br /> starting test: <br /> Test Start Time: 12:20 pm 12:20 pm 12:02 pm 12:20 pm <br /> Initial Reading(Rt): 3.8947 4.7229 5.5720 4.4016 <br /> Test End Time: 12:35 pm 12:35 pm 12:17 pm 12:35 pm <br /> Final Reading(RF): 3.8756 4.7224 5.5719 4.9014 <br /> Test Duration: 15 min. 15 min. 15 min. 15 adn. <br /> Change in Reading(RF-RO: -0.0191 -0.0005 -0.0001 -0.0002 <br /> Pass/Fail ThreslroId or <br /> Criteria: .002" 4.0.002" +/-0 002" +/-0.002" <br /> Test Result: Pass 17 Fail M Pass Fail El Pass Fail IM Pass Fail <br /> CO111111entS—(include information on repairs made prior to testing.and recommended follow-up forfailed testa) <br /> 87 vapor and 91 fill buckets have cracks. Need to be replaced. (5 gallon CNI buckets) <br /> 91 fill bucket was not tested due to cracks <br /> TOTAL P.09 <br />