Laserfiche WebLink
MAY-16-2008 19:11 Service Station Systems 408 938 8888 P.05 <br /> 5. SPILUOVERFILL CONTAINMENT BOXES <br /> Facility is Not Equipped With Spill/Overfill Containment Boxes El <br /> Spill/Overfill Containment Boxes are Present,but were Not Tested ❑ <br /> Test Method Developed By: ❑Spill Bucket Manufacturer 0 Industry Standard ❑Professional Engineer <br /> ❑ Other(Specify) <br /> Test Method Used: ❑Pressure ❑Vacuum ®Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: Incon Sump Tester Equipment Resolution: +/-0.002" <br /> Vapor Spill Box#87 Fill Spill Box#91 <br /> Bucket Diameter: <br /> Bucket Depth: 14" 14" <br /> Wait time between applying <br /> pressure/vacuum/water and 10 min, 10 min, <br /> starting test: <br /> Test Start Time: 4:25 pm 2:26 pm <br /> Initial Reading(Ri): 5.9471 63741 <br /> Test End Time: 4:40 pm 2:41 pm <br /> Final Reading(RF): 5.9435 6.1451 <br /> Test Duration: 15 min. 15 min. <br /> Change in Reading(RF-R): -0.0036 -0.2290 <br /> Pass/Fail Threshold or +/-0.002" +/-0.002" <br /> Criteria <br /> Test Result: Pass O Fail Pass ©Fail <br /> COMMentS—(include In ornwrion on repairs made prior to tesnn , and reconemended follow-up forfailed tests) <br /> Repaired 91 fill bucket with new compression gasket.Repaired 87 vapor bucket with new vapor adaptor gasket, <br /> Inspector had us fill buckets to grade (apex. 7 gallons)on 4/17/08—both failed <br /> TOTAL P.05 <br />