Laserfiche WebLink
Site Tested Test performed by <br /> GilbNR Testing Product and Vapor Overfill Containment Service Station Systems <br /> Safeway 2707 680 Quinn Ave. <br /> 6425 N. Pacific Ave. Test Results San Jose, CA 95112 <br /> Stockton, CA 95207- License#: 485184 <br /> Tech: Randy Wilkerson <br /> Test Date:6/16/10 <br /> Test Method Developed By: ❑Spill Bucket Manufacturer ®Industry Standard ❑Professional Engineer ❑Other(Specify) Test Method Used: ®Hydrostatic ❑Other(Specify) <br /> Test Equipment Used:Measuring Tape Equipment Resolution:1/16 in Example-1/8"increments I Pass/Fail Threshold or Criteria: Zero Loss <br /> Product Fill Bucket Vapor Fill Bucket <br /> Walt Time Pass Pass <br /> Tank/Grade (min) Start Stop (hre.) Gal. Depth Initial-Final=Change /Fall I Gal. Depth Initial-Final=Change /Fail <br /> 01 -Regu 5 12:00pm 1:00pm 1.00 5 15.00 14.25-14.25=0.00 Pass <br /> 02-Prem 5 12:00pm 1:00pm 1.00 5 15.00 14.50- 14.50=0.00 Pass <br /> 03-Diesel 5 12:00pm 1:00pm 11.00 5 15.00 14.63-14.63=0.00 Pass <br /> Comments: Include information on repairs made prior to testing, and recommended follow-up for failed tests. <br />