Laserfiche WebLink
must be built by the Pump manufacturer, pumps utilizing third party motor <br /> manufacturers are not considered equal. <br /> The motor shall be designed for continuous duty handling pumped media of 40 C (104 <br /> F) and capable of no less than 30 starts per hour. Motor will be suited for pressure <br /> sewer system hydraulic conditions. The rotor bars and short circuit rings shall be made <br /> of cast aluminum. Thermal switches embedded in the stator for permanent connection <br /> in the control panel shall be included. When temperatures in the coils reach 125 C (260 <br /> F) the switches will open and the motor will stop, when the motor sufficiently cools the <br /> switches will automatically close and the motor will start. <br /> The motor is sufficiently cooled by the surrounding environment or pumped media. <br /> The use of a water cooling jacket is not required. To reduce the risk of environmental <br /> concerns and the expense of disposal oil filled motors are not accepted. <br /> 2.06 Cable Entry System <br /> The cable entry seal design shall preclude specific torque requirements to insure a <br /> watertight and submersible seal. The cable entry shall consist of a single cylindrical <br /> elastomer cable gland, flanked by washers, all having a close tolerance fit against the <br /> cable outside diameter and the entry inside diameter and compressed by the body <br /> containing a strain relief function, separate from the function of sealing the cable. The <br /> assembly shall provide ease of changing the cable when necessary using the same entry <br /> seal. Epoxies, silicones, or other secondary sealing systems make it difficult to replace <br /> power cable and shall not be considered acceptable. <br /> 2.07 Motor Starting Controls <br /> All necessary motor starting components should be located in the control panel for ease <br /> of serviceability. Pumps that require removal from the wet well to repair or replace <br /> start components are not acceptable due to the additional maintenance requirements. <br /> Single phase motors shall utilize separate start and run capacitors to maximize starting <br /> torque and running efficiency. <br /> 2.08 hc-vel Controls <br /> Optional A: <br /> Pump hall operate by a Flygt level control system with a 3 point probe for tomatic <br /> level con The probe shall be constructed from uPVC 32mm tubin moulded <br /> sensor units egular intervals along the probe. Each sensor um be PVC injected <br /> to prohibit Ingres f moisture, and the sensor material will b vesta SMO254 stainless <br /> steel. Sensors will be aced along the length of the pro ssembly, and each will be <br /> individually connected to correspondingly number VC/PVC .75mm flexible cable. <br /> The moulded sensor unit ' ntain two Aves ensors mounted on opposite sides of <br /> sensor unit. Each Avesta sensor ' be 24 high and no wider than 2mm, and will <br /> protrude from the surface of the PV e probe shall be pressure injected with an <br /> epoxy resin to encapsulate all int al c onents and connections to form a rigid, <br /> homogenous unit. Eachsens unit cont ' the two Avesta sensors will be rotated <br /> 90 degrees to the previo sensor unit to elimin tracking between sensors. The cable <br /> will be encoded wit umber and text along the ent y of the cable and at intervals not <br /> greater than 2 , for identification. This cable will dark blue in colour, with the <br /> cores ligh ue. The flexible cables shall be capable of sup ting the weight of the <br /> prob d cable, without the need for additional support. The le shall be secured to <br /> 4 <br />