Laserfiche WebLink
Pacific Environmental Systems, LLC. Testing methods performed in concert with <br /> Con Vault website instructions (ConVault only) and as applied to other tanks, in <br /> conjunction with STISP001 inspection standards results as applied to those fuel storage <br /> aboveground tanks located at this facility. <br /> ', , Doan'^urkuiins q': <br /> Generrtor system <br /> ConVault (Tank <br /> Unleaded <br /> Product Gasoline ' It Diesel'.Fuel # <br /> Media N/A , ,X <br /> Initial Vacuum SH Vacuum <br /> RESULTS <br /> 15 min reading SHg Vacuum <br /> 30 min.reading SHg Vacuum Vacugfn <br /> 45 min readingSH Vacuum K= 5 V 4m <br /> 1 hr reading 5-gvacuum <br /> OTHER METNODS <br /> OMNTEC-BOA-PDS - n� <br /> DISCRIMINATING SENSOR- No hydrocarbon Bjo hydrocarbon " <br /> IN ANNULUS product detected .P_ .. �.....7 <br /> BOROSCOPE CAMERA No liquid detected No dilgtecledp' <br /> Dipstick into annulus No It uid detected No R qtd detected <br /> Visual Inspection direct No liquid detected 'd <br /> Fk for Continued Service? Yes ''fin ym 4 <br /> Conclusions &Recommendations: <br /> The next recommended formal external inspection for all WAS 20 years from the date of this <br /> inspection in accordance with the requirements of the EPA and CA regulations and that within <br /> the SPCC Plan,provided all required monthly and annual inspections are performed. <br /> Inspection Schedule <br /> All tanks inspected meet the requirements to be listed as Category 1 as they each have Spill <br /> Control and CRDM, as detailed in the STI Standard for Inspection of Aboveeround Storage <br /> Tank SPOOL Issued January 2018 a Edition. <br />