Laserfiche WebLink
MONITORING AND REPORTING PROGRAM -3- <br /> DEFENSE DISTRIBUTION REGION WEST TRACY <br /> SAN JOAQUIN COUNTY <br /> Type of Sampling <br /> Constituents Units Sample Frequency <br /> Average Flow Rate gpm Meter Plan B <br /> (since last sample) <br /> Pressure at Time psig Meter Plan B <br /> of Sampling <br /> HOLDING POND DIVERSION PIPELINE MONITORING: <br /> The diversion line from the air stripper to the storm drain holding pond shall <br /> be monitored in accordance with the following: <br /> Type of Sampling <br /> Constituents Units Sample Frequency <br /> Total Volume of gallons Meter Daily <br /> Water Transported <br /> Flow Rate at Time gpm Meter Daily <br /> of Sampling <br /> Average Flow Rate gpm Meter Daily <br /> (since last sample) <br /> Pressure at Time psig Meter Daily <br /> of Sampling <br /> EXTRACTION WELL MONITORING: <br /> During the extraction of ground water, the extraction wells EW-1 , EW-2, EW-3, <br /> EW-4, EW-5, and EW-6, shall be monitored as follows: <br /> Type of Sampling <br /> Constituents Units Sample Frequency <br /> Volatile Organics N9/l Grab Plan D <br /> (Methods 8010 and 8020) <br /> Specific Conductivity pnhos/cm Grab Plan D <br /> pH pH Units Grab Plan D <br /> Temperature °F/°C Grab Plan D <br />